HRX-OM-R026
Chapter 5 Display and setting of various functions
5.20
Alarm customizing function
HRSH Series
5-56
Changing of circulating fluid discharge pressure rise Setting and checking
12.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge pressure rise is displayed on the
digital display.
13.
Select changing of circulating fluid discharge pressure rise from the table below with [
▲]
key or [
▼] key, and confirm by pressing “SEL”.
Table 5.20-13
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
Detection pressure for circulating fluid discharge pressure rise Setting and checking
14.
Press the [SEL] key once.
The set screen of detection temperature for circulating fluid discharge pressure rise is
displayed on the digital display.
15.
Select detection pressure for circulating fluid discharge pressure rise from the table
below with [
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.20-14
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of the circulating fluid discharge
pressure rise is OFF.
MPa
Sets detection pressure for the circulating
fluid discharge pressure rise.
Pressure unit is MPa : Setting unit is
0.01MPa
Pressure unit is PSI : Setting unit is 1PSI
to
PSI
to
PV
SV
PV
SV