Chapter 5 Display and setting of various functions
5.17
Pump operation mode function
HRSH Series
5-40
1.
Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for key-lock [
] appears on the
digital display.
Pump operation mode
2.
Press the [SEL] key 23 times.
The set screen of pump operation mode is displayed on the digital display.
PV
SV
3.
Select the pump operation mode from the table below with [
▲] key or [▼] key, and
confirm
by pressing “SEL”.
Table 5.17-2
List of set value
Set value
Explanation
Initial value
(Default setting)
Pressure controlled mode
Frequency set mode
Circulating fluid discharge pressure
4.
Press the [SEL] key once.
The set screen of circulating fluid discharge pressure is displayed on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
[MENU]
Press and
hold
[MENU]
Press and
hold