HRX-OM-R026
Chapter 5 Display and setting of various functions
HRSH Series
5.20
Alarm customizing function
5-47
Table 5.20-2 Alarm setting and customizing (2/4)
Code
Alarm name
①
Alarm operations
②
Alarm threshold and others
Display
A.S
T
P
A.RUN
P
.RUN
O
F
F
Display
Default
setting
Settable range
AL04
Circulating
fluid
discharge
temp.
drop
● ○ - ●
Set temperature
1.0
o
C
(33.8
o
F)
(----)
5
1.0 to 39.0
o
C
(33.8 to 102.2
o
F)
Monitoring method
0
0 to 3
Monitoring start timer
----
(
0
)
6
0 to 600 minutes
Range over detection timer
5
5
to
999
seconds
AL05
High
circulating
return temp.
-
○ -
-
-
-
-
AL06
High
circulating
fluid
discharge
pressure
-
○ -
-
-
-
-
9
AL07
Abnormal
pump
operation
-
○ -
-
-
-
-
9
AL08
Circulating
fluid
discharge pressure
rise
● ○ - ●
Set pressure
0.55MPa
(80PSI)
(----)
7,9
0.05 to 0.60MPa
(7 to 87PSI)
AL09
Circulating
fluid
discharge pressure
drop
● ○ - ●
Set pressure
0.05MPa
(7PSI)
(----)
8,9
0.05 to 0.60MPa
(7 to 87PSI)
AL10
High
compressor
suction temp.
● - ○ -
-
-
AL11
Low
compressor
suction temp.
● - ○ -
-
-
AL12
Low
super heat
temperature
● - ○ -
-
-
AL13
High
compressor
discharge pressure
● - ○ -
-
-
AL15
Refrigerant circuit
pressure
(high
pressure side) drop
● - ○ -
-
-
AL16
Refrigerant circuit
pressure
(low
pressure side) rise
● - ○ -
-
-
4: Values in
゚
F are displayed when SE12 is F, and PSI are displayed when SE13 is PSI.
5: The default setting when AS05 is OFF.
6: The default setting when AS21 is 2 or 3.
7: The default setting when AS07 is OFF.
8: The default setting when AS09 is OFF.
9:
AL06, AL07, AL08, AL09 are disabled when AS25 is set to A.RUN. (AL06, AL07, AL08, and AL09
will not be generated)