10.4 Ethernet IP Information webpage
The Ethernet IP webpage displays information pertaining to the connection between the Netx
Controller and the PLC
.
1. This field shows the IP address of the client PLC currently connected to the Netx Control
Unit on port 44818. If there isn’t a PLC connection this field will say, ‘No current
connection’. Although the PLC connects on port 44818, the actual data I/O is sent and
received on port 2222.
2. This field shows the client UDP port used for transferring I/O data between the PLC and
the Netx Control Unit. This is a fixed port number and is always 2222.
3. This field shows the client data size in words. The size is a fixed length of 46 words.
4. This field shows the current mode of the PLC. The two possible values for this field are
‘RUN’ and ‘PROGRAM’.
5. These two fields show the requested packet interval (RPI) in milliseconds from the PLC
to the Netx (on the left) and Netx to PLC (on the right). 100ms is the minimum value
allowed for both parameters.