E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Blocking codes
Block-
ing
code
Error
Description
Cause
Solving
100
WD_ERROR_
RAM
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
101
WD_ERROR_
ROM
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
102
WD_ERROR_
STACK
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
103
WD_ERROR_
REGISTER
Internal software error
wrongly program-med
BCU or PB
reset BCU or replace BCU
and or display unit
104
WD_ERROR_ XRL
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
105
HIGH_TEMP_
ERROR
T_Supply sensor
measures over
Stay_Burning_Temp
for a period of
Max_Value_Period.
not enough waterflow
overheat exchanger
check functioning of the
circulator.
check/open all valves that
might restrict the water
flow through the unit.
check for external system
circulator that influences
flow through the unit.
check if system resistance
exceeds the spare
capacity of unit circulator.
106
REFHI_TOO_
HIGH
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
107
REFHI_TOO_ LOW Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
108
REFLO_TOO_
HIGH
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
109
REFLO_TOO_
LOW
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
110
REFHI2_TOO_
HIGH
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
111
REFHI2_TOO_
LOW
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
112
REFLO2_TOO_HI
GH
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
113
REFLO2_TOO_LO
W
Internal hardware error wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
114
FALSE_FLAME
Flame is detected in a
state in which no flame
is allowed to be seen
wrong earthing of
BCU and boiler
check earthing of BCU
and boiler
116
LOW_WATER_PR
ESSURE_
SENSOR
Low water pressure,
occurs when the
pressure drops below
Minimal_Pressure, or
when the pressure
drops below 11.6 psi.
not enough water
pressure
fill up the system and
check if there are any
water leakages
118
WD_COMM_
ERROR
Watchdog
communication error
wrong programmed
BCU or PB
reset BCU or replace BCU
and or display unit
119
RETURN_ OPEN
Return sensor open
malfunctioning return
sensor or not
connected
check connection to BCU
or check resistance NTC
sensor
120
SUPPLY_ OPEN
Supply sensor open
malfunctioning supply
sensor or not
connected
check connection to BCU
or check resistance NTC
sensor
122
DHW_OPEN
DHW sensor open
malfunctioning DHW
sensor or not
connected
check connection to BCU
or check resistance NTC
sensor
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......