E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
105
Relevant variables
Specific Parameters
Display
menu #
Level
(Default)
Value
Range
DHW_Mode
PB 1
Installer
0
0, 1, 2,3, 4, 5, 6, 7, 8
DHW_Store_Setpoint
Sets the supply temperature from the
boiler to prepare DHW in the indirect tank
PB 115
User
122
º
F
(50
º
C)
104
…
185
º
F (40
…
85
º
C)
DHW_Priority
PB 42
Installer
2
0=Time, 1=OFF, 2=ON
DHW_Max_Priority_Time
Sets the maximum time for either DHW or
CH priority.
PB 43
Installer
60 min.
DHW_Post_Pump_Period
PB 44
Installer
20 sec.
10...900
I
NSTANTANEOUS WATER HEATING WITH PLATE HEAT EXCHANGER
;
DHW
MODE
5
This is the only mode available for Combi boilers (VGH-CO).
The other DHW modes are not available for Combi boilers.
In DHW mode 5 the water flow through a plate heat exchanger is checked with a DHW-out sensor and a rotary
switch. In this DHW mode the DHW-sensor is used for modulating the burner to the required DHW setpoint. The
rotary switch is used for detecting tap demand and detecting whether the burner can stay ON.
Specific Parameters
Display
menu #
Level
(Default)
Value
Range
DHW_Mode
PB 1
Installer
0 for CH
5 for CO
0, 1, 2,3, 4, 5, 6, 7, 8
DHW_Setpoint
Sets the desired DHW temperature
PB 48
User
122
º
F
(50
º
C)
86
…
176
º
F
(30
…
80
º
C)
A
NTI
-
LEGIONELLA PROTECTION
This option is only available for Heating Only boilers (VGH-CH).
Anti-Legionella is enabled for CH-boilers for the DHW mode with an external tank with a sensor (DHW Mode 1).
To prevent legionella a special function is implemented in the software.
When DHW Mode 1 is selected the Anti-Legionella protection will be checked on the T_DHW_Out sensor. At least
once every 168 hours (7 days) the Anti_Legionella_Sensor must reach a temperature above
Anti_Legionella_Setpoint for a time specified by Anti_Legionella_Burn_Time.
If 7 days have passed and these conditions are not met, the boiler is forced to heat-up the system for Anti-Legionella.
When the Anti_Legionella_Sensor temperature is below Anti_Legionella_Setpoint the control switches ON the
circulators, when the Anti_Legionella_Sensor temperature is above Anti_Legionella_Setpoint plus 9 °F (plus 5 °C)
the control stops the circulators.
When DHW Mode 1 has been selected, the setpoint of the boiler will be at Anti_Legionella_Setpoint plus
DHW_Store_Supply_Extra.
If the supply temperature drops below the Boiler_Setpoint the boiler is started as well. The boiler is PID controlled
towards the Boiler_Setpoint. When the supply temperature rises above the boiler setpoint plus the
DHW_Supp_Hysterese_Up the boiler is switched OFF.
Every time an Anti-Legionella demand has ended the Anti_Legionella_Active_Counter is incremented to indicate
how many Anti- Legionella actions have been performed. Also, the Anti_Legionella_Wait _ime is started in order to
delay the next Anti-Legionella cycle.
The anti-legionella demand has priority over any DHW and CH demand. However, when the anti-legionella
protection is active and there is no heat or burn demand because the Anti_Legionella_Sensor is already at a high
enough temperature CH/DHW demand will be accepted as normal.
Parameters are factory set.
Parameter
Factory Setting.
Anti_Legionella_Setpoint
Setpoint for Anti-Legionella demand
140
º
F (60
º
C)
Anti_Legionella_Burn_Time
30 Min.
Anti_Legionella_Wait_Time
Wait time for Anti-Legionella demand
120 min after cold start, 168 h after first successful
Anti-Legionella demand
Table 11.19
Table 11.20
Table 11.21
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......