E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
99
Boost function
The outdoor reset boost function increases the CH_Setpoint by a prescribed increment (Boost_Temperature_Incr)
if a demand for heat continues beyond the pre-set time limit (Boost_Time_Delay).
Boiler Parameters
(25) Warm Weather Shutdn 72 °F
▲
(26) Boost Temp increment 32 °F
(27) Boost Time Delay
20 min
(28) Night Setback Temp. 40 °F
▼
These are parameters 26 Boost Temp Increment and 27 Boost Time Delay.
They have a default value of 32 °F and 20 min, so the function is switched off and can be activated by the installer
by increasing parameter 26 by a number of degrees. Also, the time can be set when this parameter will be active
in parameter 27 (now set at 20 min).
CH_Setpoint increases again if the demand for heat still is not satisfied in another time increment.
Setpoint adjustment
It is possible to adjust the calculated setpoint with parameter CH_Setpoint_Diff. The calculated setpoint can be
increased or decreased with a maximum of 50 °F (10 °C). The CH setpoint limits (Reset_Curve_Boiler_Minimum
and Reset_Curve_Boiler_Maximum) are respected while adjusting the setpoint.
Apart from the calculated setpoint the functionality is the same as described in paragraph 11.8.1.
Adjustable Outdoor Reset parameters
Parameters
display menu #
Level
Default Value
Range
CH_Mode
PB1
Installer 1
Mode 0-5
Reset_Curve_Design_Boiler
Sets high boiler CH setpoint when outdoor
temperature is equal to
Reset_Curve_Outdoor_Design.
PB19
Installer 176 ºF (80 ºC)
32…..176 ºF
(0…..80 ºC)
Reset_Curve_Outdoor_Design
Sets the outdoor temp at which the boiler
setpoint must be high as set by
Reset_Curve_Design_Boiler.
PB20
Installer 23 ºF (-5 ºC)
-4…..41 ºF
(-20…..5 ºC)
Reset_Curve_Boiler_Mild_Weather
Sets low boiler CH setpoint when outdoor temp.
is equal to
eset_Curve_Outdoor_Mild_Weather.
PB21
Installer 104 ºF (40 ºC)
32…..104 ºF
(0…..40 ºC)
Reset_Curve_Outdoor_Mild_Weather
Sets the outdoor temp at which the boiler
setpoint must be low as set by
Reset_Curve_Mild_Weather.
PB22
Installer 68 ºF (20 ºC)
32…..86 ºF
(0…..30 ºC)
Reset_Curve_Boiler_Minimum
Sets the lower limit for the CH setpoint
(minimum).
PB23
Installer 68 ºF (20 ºC)
68…..194 ºF
(20…..90 ºC)
Reset_Curve_Boiler_Maximum
Sets the upper limit for the CH setpoint
(maximum).
PB24
Installer 185 ºF (85 ºC)
68…..194 ºF
(20…..90 ºC)
Warm_Weather_Shutdown
Set max. outdoor temp. Above this temperature
heat demand is blocked.
PB25
Installer 72 ºF (22 ºC)
32…..95 ºF
(0…..35 ºC)
Boost_Temperature_Incr
CH setpoint increment when heat demand
remains beyond
Boost_Time_Delay.
PB26
Installer 32 ºF (0 ºC)
32…..68 ºF
(0…..20 ºC)
Boost_Time_Delay
PB27
Installer 20 min.
1 – 120 min.
CH_Setpoint_Diff
Adjusts the calculated CH setpoint.
PB185
User
0 ºF (0 ºC)
-18…..18 ºF
(-10….10 ºC)
Status variables
Range
Actual_CH_Setpoint
Calculated CH setpoint, based on outdoor reset curve
68...194 ºF
(20.....90 ºC)
Figure 11.20
Table 11.10
Table 11.11
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......