E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
87
Programmable in- and outputs
It is possible to re-program some in- and outputs to other functions. To do this use the list below and go to:
Menu\settings\boiler settings\"1122" (installer password)\boiler parameters.
Boiler parameter
Name
Default
setting CH
Default
setting CO
Description
Terminal
117
Prog. Input 2.
2
1
DHW flow switch/sensor
LV 16-17-18
122
Prog. Input 7.
3
3
Cascade sensor
LV 3-4
124
Prog. Input RT.
1
1
Room thermostat on
LV 12-13
125
Prog. Output 1.
4
4
System pump
HV 4-PE-5
126
Prog. Output 2.
9
9
Ext. Igniter
separate connector
127
Prog. Output 3.
6
6
Alarm semi-conductor output
HV 10-11
128
Prog. Output 4.
18
N.A.
3-way Valve DHW
HV 1-2-3-PE
To all outputs following applies: maximum current 2 A each output.
Total output of all currents combined maximum 3.5 A.
The inrush current of the 3-way valve and/or circulators is maximum 8 A.
para-
meter
Display:
INPUTS:
re-mark para-
meter
Display:
OUTPUTS
:
re-mark
(117)
Prog. Input 2.
0 Disabled
(127)
Prog. Output 3. 0 Disabled
1 DHW flow sensor
CO
1 Module pump
2 DHW flow switch
CH
2 CH pump
3 CH flow sensor
not used
3 DHW pump
4 CH flow switch
not used
4 System pump
5 Cascade pump
6 Alarm relay
CH/CO
2)
para-
meter
Display:
INPUTS:
re-mark
7 Filling valve
(122)
Prog. Input 7.
0 Disabled
8 LPG tank
1 T_Flue_2 sensor
not used
9 Ext. Igniter
2 T_Flue_2 with blocked flue
not used
10 Air damper
3 Cascade sensor
CH/CO (128)
Prog. Output 4. 0 Disabled
4 Blocked Flue switch
not used
1 Module pump
5 CH Sensor
not used
2 CH pump
(124)
Prog. Input RT. 0 Room thermostat off
3 DHW pump
1 Room thermostat on
CH/CO
4 System pump
Display:
OUTPUTS
:
5 Cascade pump
(125)
Prog. Output 1. 0 Disabled
6 Alarm relay
1 Module pump
7 Filling valve
2 CH pump
8 LPG tank
3 DHW pump
9 Ext. Igniter
4 System pump
CH/CO
10 Air damper
5 Cascade pump
11 empty
6 Alarm relay
12 empty
7 Filling valve
13 empty
8 LPG tank
14 empty
9 Ext. Igniter
15 empty
10 Air damper
16 empty
(126)
Prog. Output 2. 0 Disabled
17 3-way Valve CH
1 Module pump
18 3-way Valve DHW
2 CH pump
19 3-way Valve CH
(power when idle)
3 DHW pump
20 3-way Valve DHW
(power when idle)
CH / CO
4 System pump
5 Cascade pump
6 Alarm relay
7 Filling valve
8 LPG tank
9 Ext. Igniter
1)
CH/CO
10 Air damper
Table 10.8
Table 10.9
NOTICE
Remarks:
1) Prog. output 2: (ext. igniter); this is a separate connector,
the pin in the middle is for ionization, it has no PE
connection. If ground is needed, it must be connected to
the main ground terminal.
2) Prog. output 3: (alarm relay); this is a triac output with an
active voltage of 120 VAC, it can only handle resistive
loads between 5 and 50 Watt.
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......