Stainless steel vent
This product has been approved for use with stainless steel using the manufacturers listed.
Approved stainless steel vent pipe and fittings.
Supplier
Type
Duravent
FasNSeal, FasNSeal Flex
Security Chimneys
Secure Seal SS/SSD/SSID
Heat Fab
Saf-T EZ Seal
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking
precaution to ensure no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially
designed adapters and sealing method, see manufacturer’s instructions.
Use only the materials, vent systems, and terminations listed.
DO NOT mix vent systems of different types or manufacturers. Failure to comply could result
in severe personal injury, death, or substantial property damage.
•
The installer must use a specific vent starter adapter at the flue collar connection,
supplied by the vent manufacturer to adapt to its vent system.
•
Installations must comply with applicable national, state, and local codes. Stainless steel
vent systems must be listed as a UL-1738 approved system for the United States and a
ULC-S636 approved system for Canada.
•
Installation of a stainless-steel vent system must adhere to the stainless-steel vent
manufacturer’s installation instructions supplied with the vent system.
Approved Stainless Steel Terminations.
Duravent
Security Chimneys
HeatFab
FasNSeal
Secure Seal
Saf-T EZ Seal/ EZ 316
Boiler
Termination
Termination
Termination
VGH-80-CH / VGH-90-CO
VGH-100-CH / VGH-120-CH
VGH-150-CO / VGH-150-CH
VGH-180-CH / VGH-200-CO
FSBS3 (bird screen wall)
part.nr. 300236
FSRC3 (rain cap roof)
part.nr. 300325
SS3STAU
(screen termination)
SS3RC
(rain cap roof)
5390CI
(horizontal termination)
5300CI
(rain cap)
Sealed Combustion Air supply
When an air supply pipe is connected from the outside of the building to the boiler, the boiler will operate as a
sealed combustion boiler.
The air supply duct can be made of PVC, PP or Stainless steel
C
OMBUSTION AIR QUALITY
Combustion air must be free of contaminants. Do not install the intake for the combustion air venting in an area
which contains corrosive or other contaminants as outlined in section 9.8.1, especially Table 9.11 and Table 9.12.
A
IR SUPPLY THROUGH HUMID AREAS
When the combustion air pipe will run through an area with high humidity (for example: greenhouses), a double
walled supply pipe or an insulated duct must be used to prevent the possible condensation on the outside of the
pipe. It is not possible to insulate the internal air pipes of the boiler and therefore condensation at the internal air
canals must be prevented.
When the intake combustion air is terminated vertically through a roof an approved termination designed to prevent
water from entering into the combustion air pipe must be used.
Table 9.11
Table 9.12
NOTICE
WARNING
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......