E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
115
Lock
out
code
Error
Description
Cause
Solving
16
FLUE_GAS_
ERROR
Flue temperature
exceeded the maximum
flue temperature
there is no water in
the heat exchanger
or flue gas sensor is
malfunctioning or
heat exchanger is
overheated.
check if flue sensor is
working correctly if not so
replace flue sensor. Check
waterflow if to low increase
waterflow.
17
STACK_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
18
INSTRUCTION_
ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
19
ION_CHECK_
FAILED
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
20
FLAME_OUT_
TOO_LATE
Flame still present 10 sec.
after closing the gas valve
wrong earthing of
BCU and boiler
check earthing of BCU and
boiler
21
FLAME_
BEFORE_IGNIT
Flame is detected before
ignition
wrong earthing of
BCU and boiler
check earthing of BCU and
boiler
22
TOO_MANY_
FLAME_LOSS
Three times flame lost
during 1 demand
bad gas supply or
CO
2
level is not
correct or bad
ignition rod
check gas supply pressure,
check CO
2
level and adjust
if necessary, replace igni-
tion rod or replace ignition
cable.
23
CORRUPTED_
ERROR_NR
Error code RAM byte was
corrupted to an unknown
error code.
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
27
FILLING_TOO_
MUCH
Too many automated
filling attempts in a short
time period
if output is
programmed as filing
valve and there are
too many filing
attempts
check if there is a leak in
the central heating system
or if the boiler itself is
leaking also check
expansion vessel on
internal leak
28
FILL_TIME_
ERROR
Filling takes too long
if output is
programmed as filing
valve and filling takes
more than 10
minutes
check if there is a leak in the
central heating system or if
the boiler itself is leaking
also check expansion
vessel on internal leak
29
PSM_ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
30
REGISTER_
ERROR
Internal software error
wrongly programmed
BCU or PB
reset BCU or replace BCU
and or display unit
32
T_EXCHANGE_
DIFF_ERROR
The 2 exchange sensors
deviate too much for more
than 60 seconds
there is not enough
water flow through
the heat exchanger
check if the general pump is
running and if all valves are
open to make enough flow
33
LWCO_1_
ERROR
Low water cut off 1 error
there is no water in
the heat exchanger
or not electrically
connected
check if there is enough
water in the heat exchanger
if not: fill up the system
34
LWCO_2_
ERROR
Low water cut off 2 error
there is no water in
the heat exchanger
or not electrically
connected
check if there is enough
water in the heat exchanger
if not: fill up the system
35
APS_NOT_
CLOSED_IN_
POST_PURGE
Air pressure switch not
closing during post-purge
1
no air transport to the
burner after heating
de-mand; flue or air
inlet is blocked or
APS is jammed or air
signal hose not
connected to the air
intake pipe or water in
hose
check if there are any
obstructions in the flue or
air intake, replace APS if
jammed, connect air hose
to the air intake pipe,
remove any water from the
hose.
Table 13.1
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......