E93.1901EN032 Installation and Service Manual SlantFin VGH-CH / CO
Menu structure display
Menu structure Display:
Access
level
Description:
1. Central Heating (CH)
User
Enter the Central Heating (CH)
menu
2. Domestic Hot Water (DHW)
User
Enter the Domestic Hot Water
(DHW) menu
3. Information
User
Enter the Information menu
4. Settings
User
Enter the Settings menu
5. System Test
User
Enter the System Test menu
(see chapter 15).
1. Central Heating (CH)
min.
max.
Default unit
Access
level
Description:
1.1 CH Setpoint
68
(20)
194
(90)
176
(80)
°F
(°C)
Installer
Set the CH setpoint if CH mode is 0
1.2 Outdoor Reset
User
Enter the Outdoor Reset menu if
CH mode is 1
1.2 Outdoor reset
min.
max.
Default
unit
Access
level
Description:
Design Supply T.
68
(20)
194
(90)
176
(80)
°F
(°C)
Installer
Set CH setpoint when outdoor
temperature equals Des. Outd. T.
Base Supply T.
68
(20)
194
(90)
104
(40)
°F
(°C)
Installer
Set CH setpoint when outdoor
temperature equals Bas. Outd. T.
WW Shutdown
32
(0)
95
(35)
72
(22)
°F
(°C)
Installer
Set outdoor temperature above
which CH demand is locked.
Bas. Outd. T.
32
(0)
86
(30)
68
(20)
°F
(°C)
Installer
Set the outdoor temperature at
which CH setpoint is set to Bas.
Supply T.
Des. Outd. T.
-13
(-25)
77
(25)
23
(-5)
°F
(°C)
Installer
Set the outdoor temperature at
which CH setpoint is set to Des.
Supply T.
2. Domestic Hot Water
(DHW)
min.
max.
Default
unit
Access
level
Description:
DHW Setpoint
104
(40)
160
(71)
122
(50)
°F
(°C)
Installer
Set the DHW setpoint
DHW Store Setpoint
104
(40)
160
(71)
122
(50)
°F
(°C)
Installer
Set the DHW store setpoint for
DHW mode 1 and 2
3. Information
min.
max.
Default
unit
Access
level
Description:
3.1 Software versions
User
Enter the Software Versions menu
3.2 Boiler Status
User
Enter the Boiler Status menu
3.3 Boiler History
User
Enter the Boiler History menu
3.4 Error Log
User
Enter the Error Log menu
3.5 Service
User
Enter the Service menu
3.1 Software versions
min.
max.
Default
unit
Access
level
Description:
Display
xxxx
xxxx
User
Display the software checksum
Boiler
xxxx
xxxx
User
Display the boiler software checksum
Device Group
xxxMN
User
Display the boiler group ID
Summary of Contents for VHG-100-CH
Page 2: ......
Page 8: ...8 E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 1 SAFETY GUIDELINES...
Page 9: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 9 CONSIGNES DE S CURIT...
Page 83: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 83 Figure 10 5...
Page 85: ...E93 1901EN032 Installation and Service Manual SlantFin VGH CH CO 85 Figure 10 7...
Page 162: ......
Page 163: ......