4.
Enter parameter value 002 and press K2 (
↩
) key to save the value.
5.
Navigate to parameter 1.
6.
Enter parameter value 002 and press K2 (
↩
) key to save the value.
7.
Press K3 (
←)
key to exit and return to normal operation.
9.5.4
Display indicates “[n] - - -”
When setting parameter values, the display can indicate “[n] - - -“, where [n] is the parameter number
and dashes have replaced the parameters values. This usually means that the device has not been
properly commissioned to accept parameter values. For example, if you attempt to set parameter value
for the measurement range (parameter 3) without running Auto Setup, the displays indicate “3 - - -“.
Make sure that you have commissioned and set up the device according to instructions in chapter
Commissioning and system setup
9.5.5
No output signal
If the device does not generate a valid output signal during normal operation:
•
Make sure that the device is connected to a power source and that all electrical connections are
made correctly.
•
Make sure that the power supply is ON.
•
Make sure that normal processes are running.
•
Perform Auto Setup.
9.5.6
No response after Auto Setup
If the device does not respond after you have performed Auto Setup:
•
Make sure that the device is connected to a power source and that all electrical connections are
done correctly.
•
Make sure that the power supply is ON.
•
Make sure that normal processes are running during Auto Setup.