©2021 Sintrol.
All rights reserved.
60 (104)
Revision 4
8.1.4
Performing Auto Setup
The easiest way to perform Auto Setup is to start it manually on the main interface of the device. Only
two keys, K0 (
+
) and AUTOSETUP, are required to perform Auto Setup. The keys are highlighted in
Figure 28: Main board of the device with AUTOSETUP and K0 (+) key highlighted
To perform Auto Setup:
1.
Press K0 (
+
) key to enter MAINTENANCE mode. LEDs on both sides of the display on the front panel
of the device start to blink, alternating between green and red.
2.
Press AUTOSETUP key for 1 second. During Auto Setup:
•
The display shows the remaining time in seconds.
•
Both green LEDs continue to blink.
3.
Auto Setup is completed when the counter reaches 0. The device resumes normal operation.
Auto Setup takes 500 seconds (approximately 8 minutes) to complete.
If you want to cancel Auto Setup, press AUTOSETUP key again for 1 second.
For a more detailed description of the main interface of the device, see section
chapter
8.2
Changing parameters
8.2.1
Main interface
You can change parameters manually with the main interface of the device. The main board of the
device is equipped with six operation and navigation keys (Figure 29).