Figure 14. Programming Points
5. Click on the appropriate subpoint and define its point type, as follows. (The subpoint device
type is permanently set.)
Points 1-245
. If the device type is TRIAM (i.e., the XA device is an input/output
device), then the first subpoint is used for the output and the second point is used for the
input. Click on the Point Type drop down list and choose one of the available point
types.
If the device type is RIAM (i.e., the XA device is an output-only device), click on the
subpoint and then click on the Point Type drop down list box and choose the output point
type.
Refer to 574-849 for point type definitions
Points 246 – 255
. Devices in this address range must use the MLPTIO device type.
MLPTIO subpoints map to XA devices as listed in Table 5 below:
Output-only devices
cannot be assigned to this address range.
Click on the subpoint and then click on the Point Type drop down list box and choose the
appropriate input or output point type.
Refer to in 574-849 for point type definitions
Continued on next page
Programming the FACP as XA Loop Master,
Continued
Programming FACP
XALIC Points