12
XA DEVICES
REF
CLK
CMD
SIG
REF
CLK
CMD
SIG
REF
CLK
CMD
SIG
SHIELD
SHIELD
12 AWG (3.309 mm2)
to
18 AWG (0.8231 mm2)
Non-Power Limited
XA Loop Wiring
TB3
SHLD
SLAVE
SW2
ON | OFF
4-WIRE | 3-WIRE
SLAVE | MASTER
256 | 257
MASTER
CLASS A
CLASS B
REF
SIG
CMD
CLK
REF A
SIG A
CMD A
CLK A
SHLD
REF B
SIG B
CMD B
CLK B
Wire must be 12 AWG (3.309 mm
2
) to 18 AWG (0.8231 mm
2
), non-power limited. Wiring must
test free of all grounds. Wire as follows:
1. Route wire from the CLK B, CMD B, SIG B, REF B and SHLD outputs of the XALIC card
to the appropriate inputs on a XA Loop device.
2. Route wire from the first XA Loop device to the next one. Repeat for each appliance.
3. Route wire from the last XA Loop device to the CLK A, CMD A, SIG A, REF A and SHLD
inputs on TB3 of the XALIC.
Note:
Class A wiring is required if any of the XA loop devices are intended to serve as
initiating devices that initiate a preaction/deluge function.
Figure 9. Class A Wiring, XALIC Configured as an XA Loop Master
Continued on next page
Connecting to the XA Loop
Class A Wiring –
XALIC Configured
as XA Loop Master
firealarmresources.com