To connect the XA Loop Interface Card (XALIC) to devices using Class B wiring, do the
following.
1. On TB3 jumper REF A to REF B, SIG A to SIG B, CMD A to CMD B and CLK A to CLK
B. If the jumper is absent a XA Loop Wiring fault will be indicated.
2. Route wire from the CLK B, CMD B, SIG B, REF B and SHLD outputs of the XALIC card
to the appropriate inputs on a XA Loop device.
3. Route wire from the first XA Loop device to the next one. Repeat for each appliance.
4. Connect an End-of-Line Supervisory device at the end of the XA Loop.
Note:
This configuration shall not be used if the FACP is providing preaction/deluge
service.
Figure 10. Class B Wiring, XALIC Configured as XA Loop Master
Continued on next page
Connecting to the XA Loop,
Continued
Class B Wiring –
XALIC Configured
as XA Loop Master