11
The XALIC has a form factor of 4” x 10” (101 x 254 mm), and requires a full-length slot in an
expansion chassis. Locate an available slot for the card and use the PDI connector (P4) on the
backside of the XALIC card to connect to one of the PDI connectors on the lower row, as shown
in Figure 6 above. Secure the card to the Expansion Chassis using the supplied hardware.
Place Jumpers P1 and P2 in the leftmost position and connect the XALIC to the Aux power source
as shown in the figure below.
|RUI+|RUI-|SHLD|
|AUX+|AUX-|
JUMPERS RIGHT FOR
SIGNAL POW ER
JUMPERS LEFT FOR
AUX POW ER
TB1
TB2
P2
P1
1
1
AUX PW R NOMINAL 24VDC
(18VDC-33VDC)
Figure 7. Connecting to AUX Power
If the XALIC is installed in a backbox that contains neither a power supply (XPS, RPS, or
expansion SPS) or a PDI, it requires power from an Aux Power source and must be connected via
its RUI terminals to a TIC or Master Controller in another backbox. Aux power and RUI wiring is
supervised and power-limited. Aux power must come from either the FACP, or from a regulated,
power-limited supply that is UL-listed for Fire Protective Signaling Use.
The XALIC has a form factor of 4” x 10” (101 x 254 mm), and requires a full-length slot in an
expansion chassis. Secure the card to the backbox using the hardware supplied with the card.
Place Jumpers P1 and P2 in the leftmost position and connect the XALIC to the Aux power source
as shown in the figure below. Connect the RUI terminals on the card to the RUI terminals on a
TIC or Master Controller in a separate backbox.
3 2 1
Jumpers Right
for Signal Power
Jumpers Left
for AUX Power
RUI+
RUI-
SHLD
AUX-
AUX+
Shield
AUX Power (18-33 VDC)
TB1
TB2
Figure 8. Connecting to AUX Power and RUI
Continued on next page
Hardware Installation,
Continued
Expansion Bay Does
Not Contain XPS,
RPS, or SPS But
Backbox Contains
Master Controller or
TIC
Backbox Does Not
Contain XPS, RPS,
or SPS, and does
not Contain PDI
Note:
In this configuration, the
XALIC receives internal Panel
communications from the PDI. Do
not wire RUI communications to
TB1.
Note:
When the XALIC is installed in this
manner, the XA loop devices shall not be
programmed as inputs that serve as
initiating devices for preaction/deluge
service, if the Panel is so configured.
Wiring is supervised and
power limited
Note:
AUX power must be
provided by the Panel or
power-limited power supply
UL-listed for fire protective
signaling use.
All wiring is supervised
and power-limited.
Note:
AUX power
must be provided by
the Panel or power-
limited power supply
UL-listed for fire
protective signaling
use.