22
Figure 17. Programming Subpoint 1
e. Click on Subpoint 1. The device type is automatically set to MINPUT and cannot be
changed. Click on the Point Type drop down list box and select the appropriate point
type. (The point type determines how the control point is interpreted by the FACP. Use
Utility for Signal Silence, Reset, and Miscellaneous functions. Use FIRE to annunciate a
fire alarm from the Autocall panel to the FACP.)
f.
Add a descriptive custom label for the point.
g. Click Apply to save the changes.
Step 3. Write Custom Control.
The control point functions as an on/off switch for one or
more FACP Custom Control equations. Typical equations include the following:
System Reset.
In the following example, M2-1-1 is a input point on the 4100’s XA card. It
is linked to XA Device 1 (a switch) on the Autocall system. When XA Device 1 turns ON,
the input activates, which executes the following equation. (P212 is the Detector/System
Reset pseudo point on the FACP.)
IN:
M2-1-1 ON
OUT:
TRACK ON P202 PRI = 9,9
Continued on next page
Programming FACP as an XA Loop Slave,
Continued
Programming
Control Points