In this simple example, an FACP is replacing an existing Autocall head end with one XA Loop. It
has the following devices:
Addresses 1-15: Smoke detectors
Addresses 16-30: Pull stations
Addresses 31-35: General Alarm command receivers (on-til-silence)
The FACP is programmed with an SPS (containing one IDNet channel by default – M1) and an
XA Loop Interface Card (XALIC – M2). Since this a master configuration, the TRIAM device
type is used for the smoke detectors and pull stations, and the RIAM device type is used for the
output-only command receivers.
Address
Device Type
Point Type
1-15
TRIAM
Input: SMOKE
Output: RELAY
16-30
TRIAM
Input: PULL
Output: RELAY
31-35
RIAM
Output: SSIGNAL
FACP XA Loop Master Application Example
Overview
FACP Programming
firealarmresources.com