14
XA Loop Wiring
Non-Power Limited
From previous XA Device /
XA Master
To next XA Device
TB3
Shield
Shield
SHLD
SLAVE
SW2
ON | OFF
4-WIRE | 3-WIRE
SLAVE | MASTER
256 | 257
MASTER
CLASS A
CLASS B
REF
SIG
CMD
CLK
REF A
SIG A
CMD A
CLK A
SHLD
REF B
SIG B
CMD B
CLK B
12 AWG (3.309 mm
2
)
to
18 AWG (0.8231 mm
2
)
To connect the XA Loop Interface Card (XALIC) as a Slave on the XA Loop, do the following.
1. Route CLK, CMD, SIG, REF and SHLD from the previous XA Device / XA Master to TB3
on the XALIC card. From TB3, Route CLK, CMD, SIG, REF and SHLD to next XA device.
Note: TB3 positions 10-11, 12-13, 14-15, 16-17 are internally connected.
Figure 11. XALIC Configured as XA Loop Slave
Connecting to the XA Loop,
Continued
Wiring -- XALIC
Configured as XA
Loop Slave