Preface
1.3 Functional description
The control modules of the electrical control system M-SHEV
use bus technology to communicate with each other. In case
of an ALARM-trigger or during daily ventilation operations, the
M-SHEV controls the connected opening actuators.The
ventilation functions also serve as regular functional checks
of the smoke and heat ventilation system.
Smoke and heat extraction systems belong to the field of
preventive fire protection. By installing them, lives can be
saved in an emergency. The building permit authority decides
whether and how the smoke control system must be installed
in the building. Before proceeding with the installation, please
check once again if the size of the smoke and heat extraction
system is compliant with the official regulations in order to
ensure sufficient system functionality.
The control systems of the M-SHEV product family consist of
four components (optionally up to six):
• Power supply
(switching power supply, charging device and battery)
• Central interface ZI-100
• Sensor interface SI-100
• Motor relay MR-120
• Message interface MI-100
(optional / not included in the standard scope of delivery)
• Bus interface BI-100
(optional / not included in the standard scope of delivery)
All components are equipped with tension spring terminals
(0.5 mm² – 2.5 mm²).
Table 1: Mechanical properties M-SHEV-10-AP
Dimensions (W x H x D)
Weight (including battery)
14.3 kg
Protection rating
IP20 according to EN 60 529
Housing
Steel sheet (powder-coated)
Colour
RAL 9010
Table 2: Mechanical properties M-SHEV
Dimensions (W x H x D)
1
1.
Standard sizes; dimensions may vary according to customer
requirements.
Protection rating
2
2.
If suitable cable glands are used.
IP66 according to EN 60 529
Housing
Steel sheet (powder-coated)
Colour
RAL 7035
Table 3: Connection and operation
Connection
See Chapter 4 “Electrical
connection” on page 20.
Actuator cut-off in every position
(STOP command)
Yes
1
1.
Only in ventilation mode, without dead man's function.
Deadlock function according
prEN 12101-9 (re-triggering)
Deadlock enabled
(can be activated/deactivated
via SIMON LINK on the
MR-120)
Maximum cable length between
control unit and actuator
See Chapter 4.4 “Motor relay
– MR-120” on page 22.
Maintenance
See supplementary sheet
“Safety instructions and
warranty conditions”!
Table 4: Installation and ambient conditions
Operational temperature
-5 to 40 °C
1
1.
This temperature range applies to all components of the M-SHEV
System (incl. battery).
Storage temperature
Suitable for external installation
Only with special types of
housings – in case of doubt,
please contact our technical
sales department.
Table 5: Approvals and certificates
EU compliant
In accordance with
EMC Directive 2014/30/EU and
Low Voltage Directive 2014/35/EU.
Power supply
EN 12101-10 (Smoke and heat control sys-
tems – Part 10: Power supplies)
• M-SHEV-10-AP:
406 x 444 x 170 mm
• M-SHEV-10:
400 x 600 x 200 mm
• M-SHEV-24:
500 x 500 x 200 mm
• M-SHEV-48:
600 x 600 x 250 mm
• M-SHEV-72:
800 x 800 x 250 mm