background image

BA_M-SHEV_EN_17

www.simon-protec.com

Date: 30.07.2019

Issue: 1.7/07.2019

[email protected]

Page 5

Preface

1.3 Functional description

The control modules of the electrical control system M-SHEV 
use bus technology to communicate with each other. In case 
of an ALARM-trigger or during daily ventilation operations, the 
M-SHEV controls the connected opening actuators.The 
ventilation functions also serve as regular functional checks 
of the smoke and heat ventilation system.

Smoke and heat extraction systems belong to the field of 
preventive fire protection. By installing them, lives can be 
saved in an emergency. The building permit authority decides 
whether and how the smoke control system must be installed 
in the building. Before proceeding with the installation, please 
check once again if the size of the smoke and heat extraction 
system is compliant with the official regulations in order to 
ensure sufficient system functionality. 

The control systems of the M-SHEV product family consist of 
four components (optionally up to six):

• Power supply 

(switching power supply, charging device and battery)

• Central interface ZI-100

• Sensor interface SI-100

• Motor relay MR-120

• Message interface MI-100 

(optional / not included in the standard scope of delivery)

• Bus interface BI-100 

(optional / not included in the standard scope of delivery)

All components are equipped with tension spring terminals 
(0.5 mm² – 2.5 mm²).

Table 1: Mechanical properties M-SHEV-10-AP

Dimensions (W x H x D)

Weight (including battery)

14.3 kg 

Protection rating

IP20 according to EN 60 529

Housing

Steel sheet (powder-coated)

Colour

RAL 9010

Table 2: Mechanical properties M-SHEV

Dimensions (W x H x D)

1

1.

Standard sizes; dimensions may vary according to customer 

requirements.

Protection rating

2

2.

If suitable cable glands are used.

IP66 according to EN 60 529

Housing

Steel sheet (powder-coated)

Colour

RAL 7035

Table 3: Connection and operation

Connection

See Chapter 4 “Electrical 
connection” on page 20
.

Actuator cut-off in every position 
(STOP command)

Yes

1

1.

Only in ventilation mode, without dead man's function.

Deadlock function according 

prEN 12101-9 (re-triggering)

Deadlock enabled

(can be activated/deactivated 
via SIMON LINK on the 

MR-120)

Maximum cable length between 
control unit and actuator

See Chapter 4.4 “Motor relay 
– MR-120” on page 22.

Maintenance

See supplementary sheet 
“Safety instructions and 
warranty conditions”!

Table 4: Installation and ambient conditions

Operational temperature

-5 to 40 °C 

1

1.

This temperature range applies to all components of the M-SHEV 

System (incl. battery).

Storage temperature

Suitable for external installation

Only with special types of 
housings – in case of doubt, 
please contact our technical 
sales department.

Table 5: Approvals and certificates

EU compliant

In accordance with 

EMC Directive 2014/30/EU and 

Low Voltage Directive 2014/35/EU.

Power supply

EN 12101-10 (Smoke and heat control sys-
tems – Part 10: Power supplies)

• M-SHEV-10-AP:

406 x 444 x 170 mm

• M-SHEV-10: 

400 x 600 x 200 mm 

• M-SHEV-24: 

500 x 500 x 200 mm 

• M-SHEV-48: 

600 x 600 x 250 mm 

• M-SHEV-72: 

800 x 800 x 250 mm 

Summary of Contents for M-SHEV Series

Page 1: ...ily Copyright by SIMON PROtec Systems GmbH Subject to technical changes and errors All figures are exemplary Only valid with the supplementary sheet Safety instructions and warranty conditions Operati...

Page 2: ...0 2 4 6 Technical data ZI 100 ZI1 10 2 5 Sensor Interface SI 100 11 2 5 1 Trigger or indicating lines line monitored 11 2 5 2 Indicators 11 2 5 3 ALARM mode reset 11 2 5 4 DIP switches 11 2 5 5 Reset...

Page 3: ...time 17 2 7 3 Technical data MI 100 MI1 17 2 8 BUS Interface BI 100 optional 18 2 8 1 MODBUS 18 2 8 2 Digital inputs 18 2 8 3 Technical data BI 100 BI1 18 3 Mechanical connection 19 3 1 M SHEV 10 AP...

Page 4: ...gulation electronics for the operation of 24 V DC actuators Ventilation signals from ventilation buttons wind rain detectors and alarm triggering of three monitored indicating lines emergency button S...

Page 5: ...ties M SHEV 10 AP Dimensions W x H x D Weight including battery 14 3 kg Protection rating IP20 according to EN 60529 Housing Steel sheet powder coated Colour RAL 9010 Table 2 Mechanical properties M S...

Page 6: ...tching power supply charging device battery are used cascaded The following figures may vary depending on the size of the housing and number of modules According to EN 12101 10 both the primary switch...

Page 7: ...failure undervoltage of the power supply or if the primary power supply fails 2 1 4 Technical data rated values Table 6 Operating voltage continuous operation 230 V AC Permissible voltage range short...

Page 8: ...Fuse character type T 3 15 A Charging voltage 26 7 27 9 V DC Charging current 1 1 A Interruption time no interruption LED indicator for mains operating state Continuous green light mains present LED i...

Page 9: ...3 Internal BUS connection The individual modules of the M SHEV control panel are con nected to each other through the BUS connections RJ45 sockets 2 3 1 Terminal plugs AS 110 The AS 110 terminating pl...

Page 10: ...evaluat ed independently of each other as normally open or normally closed Two 24 V DC terminals mains backup are available to connect the inputs The respective functions are shown in the connection p...

Page 11: ...00 is provided with the following indicators Indicating line is triggered separate for B1 B2 and B3 red Failure faults of the SI 100 yellow OK operating state green 2 5 3 ALARM mode reset After a SI 1...

Page 12: ...0 SI1 Table 17 Permissible voltage range 21 28 2 V DC Power consumption standby mode 10 20 mA Power consumption ALARM mode max 80 mA Emergency button connection 7 terminals OK Y M RZ RA B1 Smoke detec...

Page 13: ...unction Basic The MR 120 module operates as standard with 3 priority levels for detection lines 1 HE button 2 smoke detector and 3 BMZ When an as signed sensor interface is triggered the MR 120 reacts...

Page 14: ...as long as the respective direction button is pressed The actuators stop as soon as the button is released If the ventilation button is touched only briefly the ventilation command is switched to cont...

Page 15: ...and closing times must be measured and then entered on site The connected actuators then move to the required position proportional to the applied supply voltage or current To ensure that this openin...

Page 16: ...ntacts A statement always consists of three elements a logical statement no entry statement is true or NOT the statement is negated the origin of the statement and the statement Origin of the statemen...

Page 17: ...ndition logical statement is true the dry contact relay is switched either as long as the condition remains true or for a preset time 1 second to 1 hour 2 7 2 c Hold time After reaching the condition...

Page 18: ...o set the parity stop bits and a watchdog function If the MODBUS communication is lost the BI 100 goes into fault mode 2 8 2 Digital inputs There are 2 digital inputs A 24 V DC terminal mains is avail...

Page 19: ...the housing s direct mounting points for the M SHEV see Figure 15 Mounting points back of housing or mount the four wall fixing lugs see Figure 16 Wall fixing lugs supplied to the housing and then ma...

Page 20: ...10 AP Figure 18 M SHEV DANGER The system must be mounted by specialist personnel qualified electricians only All relevant national safety regulations and directives apply to mounting installation and...

Page 21: ...h RM 2860 TH 4860 1 2 3 4 5 24V Wind Rain Digital Input GND E LZ A Z E 5 NO 1 2 3 NC Jumper Power Supply 4 e g central ventilation or other external control Mains Backup wind rain detector WTS OK Y M...

Page 22: ...formation for motor cable empirical formula Wire cross section mm single cable length m x number of actuators x current consumption per actuator A 73 The DIN VDE 0100 and DIN VDE 0298 regulations cont...

Page 23: ...rical fastening features i e it can be used on the right or left The lid can alternatively be equipped with a lock 5 2 M SHEV Place the pair of batteries on the bottom plate of the housing Connect the...

Page 24: ...51 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Fraunhoferstra e 14 82152 Planegg Martinsried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Mail info simon protec de Internet www simon...

Reviews: