2.5.6 Fire alarm system AUTORESET function

Generally, all SHEV-alarms must be reset manually by 
pressing the RESET button (onboard / emergency button). 
 For detection line 3 (FAS – fire alarm system), the AUTORE-
SET function can be activated, which will reset the SHEV and 
power the relays into CLOSE direction, after the FAS has 
been reset.

For an additional ventilation command CLOSE to 
be generated on the MR-120, the ventilation 
source 

SIx  

/

 Autoreset  

must be enabled on the 

MR-120.

2.5.7 Fault triggered only on power outage

If this function is enabled, a fault is indicated at 
the central interface, sensor interface and emer-
gency button only if there is a line interruption at 

the indicating lines 1 – 3.

2.5.8 Fireman’s override switch / SI-100-MASTER

This gives the fire brigade top priority and enables it to close 
windows that have already been opened in the event of an 
alarm, even if alarms are present. For this function you need 
a SI-100-MASTER module. A suitable triggering device (op-
tional) is recommended for control. Make sure that the speci-
fied current values (see Table 18 on page 12) are not 
exceeded.

To be able to use the connected fire service- 
button as fireman’s override switch, the functions 
“Fireman’s button” and “RZ triggers alarm over-

ride” must be activated in the SI-100-MASTER module. The 
SI-100-MASTER  must be assigned to the MR-120 and the 
“Accept fireman's button commands” function must be acti-
vated.

2.5.9 SI-100-SP

This variant of the SI-100 module enables the connection of 
emergency buttons with 3-wire technology (level monitoring), 
such as HE-077 or HE-083. For further information, please 
contact our technical sales department.

2.5.10 Technical data SI-100 (-SI1)

Table 17: 

Permissible voltage range

21 – 28.2 V DC

Power consumption (standby mode)

10 – 20 mA

Power consumption (ALARM mode)

max. 80 mA

Emergency button connection

7 terminals 

(OK / Y / M / – / RZ / RA / B1)

Smoke detector connection

3 terminals (B2 / – / RA)

Fire alarm system connection

3 terminals (B3 / – / RA)

DIP switch position 

(default/delivery condition)

1 – 3: ON

4: OFF

LED indicator

3 x red: “ALARM release”

yellow: “Failure”

green: “OK”

Table 18: Connection data for emergency button 

(HE buttons)

Maximum amount 

main emergency switch

1

Maximum amount 

off side switch

7

Output voltage range (B1)

17.5 V DC  – 18 V DC

Current rating (B1)

max. 120 mA

Current monitoring window 

(OK range)

100 µA to 5 mA

Output voltage range (OK)

21 V DC – 28.2 V DC

Output voltage range (Y)

21 V DC – 28.2 V DC

Output voltage range (M)

21 V DC – 28.2 V DC

Input voltage range (RA)

15 V DC – 30 V DC

Input voltage range (RZ)

15 V DC – 30 V DC

Current rating (OK)

max. 80 mA

Current rating (Y)

max. 80 mA

Current rating (M)

max. 80 mA

Table 19: Connection data for smoke detector 

(RM 3000 / RM 2860) or thermo detector (TH 4860)

Maximum amount

8 x RM 3000 

(VdS approval 
G203036) or

6 x RM 2860 / TH 4860

(VdS approval: 
G200017 / G200060)

Output voltage range (B2)

17.5 V DC – 18 V DC

Current rating (B2)

max. 120 mA

Current monitoring window (OK range)

100 µA to 5 mA

Reset time after ALARM reset 

(by disconnecting power supply B2)

3 sec

Input voltage range (RA)

15 V DC – 30 V DC

INFORMATION

The smoke detector types offered by us and listed in 
Table 19 have been tested and approved for unrestricted 
functionality with the M-SHEV product family by SIMON 
PROtec. 
We cannot guarantee that the M-SHEV product family 
works with other smoke detectors.

Table 20: Connection data of the fire alarm system 

(FAS)

)

Output voltage range (B3)

17.5 V DC – 18 V DC

Current rating (B3)

max. 120 mA

Current monitoring window (OK range)

100 µA to 5 mA

Reset time after ALARM reset 

(by disconnecting power supply B3)

3 sec

Input voltage range (RA)

15 V DC – 30 V DC

ATTENTION

If this function is enabled, no ALARM is triggered at the 
respective indicating lines 1 – 3.

Summary of Contents for M-SHEV Series

Page 1: ...ily Copyright by SIMON PROtec Systems GmbH Subject to technical changes and errors All figures are exemplary Only valid with the supplementary sheet Safety instructions and warranty conditions Operati...

Page 2: ...0 2 4 6 Technical data ZI 100 ZI1 10 2 5 Sensor Interface SI 100 11 2 5 1 Trigger or indicating lines line monitored 11 2 5 2 Indicators 11 2 5 3 ALARM mode reset 11 2 5 4 DIP switches 11 2 5 5 Reset...

Page 3: ...time 17 2 7 3 Technical data MI 100 MI1 17 2 8 BUS Interface BI 100 optional 18 2 8 1 MODBUS 18 2 8 2 Digital inputs 18 2 8 3 Technical data BI 100 BI1 18 3 Mechanical connection 19 3 1 M SHEV 10 AP...

Page 4: ...gulation electronics for the operation of 24 V DC actuators Ventilation signals from ventilation buttons wind rain detectors and alarm triggering of three monitored indicating lines emergency button S...

Page 5: ...ties M SHEV 10 AP Dimensions W x H x D Weight including battery 14 3 kg Protection rating IP20 according to EN 60529 Housing Steel sheet powder coated Colour RAL 9010 Table 2 Mechanical properties M S...

Page 6: ...tching power supply charging device battery are used cascaded The following figures may vary depending on the size of the housing and number of modules According to EN 12101 10 both the primary switch...

Page 7: ...failure undervoltage of the power supply or if the primary power supply fails 2 1 4 Technical data rated values Table 6 Operating voltage continuous operation 230 V AC Permissible voltage range short...

Page 8: ...Fuse character type T 3 15 A Charging voltage 26 7 27 9 V DC Charging current 1 1 A Interruption time no interruption LED indicator for mains operating state Continuous green light mains present LED i...

Page 9: ...3 Internal BUS connection The individual modules of the M SHEV control panel are con nected to each other through the BUS connections RJ45 sockets 2 3 1 Terminal plugs AS 110 The AS 110 terminating pl...

Page 10: ...evaluat ed independently of each other as normally open or normally closed Two 24 V DC terminals mains backup are available to connect the inputs The respective functions are shown in the connection p...

Page 11: ...00 is provided with the following indicators Indicating line is triggered separate for B1 B2 and B3 red Failure faults of the SI 100 yellow OK operating state green 2 5 3 ALARM mode reset After a SI 1...

Page 12: ...0 SI1 Table 17 Permissible voltage range 21 28 2 V DC Power consumption standby mode 10 20 mA Power consumption ALARM mode max 80 mA Emergency button connection 7 terminals OK Y M RZ RA B1 Smoke detec...

Page 13: ...unction Basic The MR 120 module operates as standard with 3 priority levels for detection lines 1 HE button 2 smoke detector and 3 BMZ When an as signed sensor interface is triggered the MR 120 reacts...

Page 14: ...as long as the respective direction button is pressed The actuators stop as soon as the button is released If the ventilation button is touched only briefly the ventilation command is switched to cont...

Page 15: ...and closing times must be measured and then entered on site The connected actuators then move to the required position proportional to the applied supply voltage or current To ensure that this openin...

Page 16: ...ntacts A statement always consists of three elements a logical statement no entry statement is true or NOT the statement is negated the origin of the statement and the statement Origin of the statemen...

Page 17: ...ndition logical statement is true the dry contact relay is switched either as long as the condition remains true or for a preset time 1 second to 1 hour 2 7 2 c Hold time After reaching the condition...

Page 18: ...o set the parity stop bits and a watchdog function If the MODBUS communication is lost the BI 100 goes into fault mode 2 8 2 Digital inputs There are 2 digital inputs A 24 V DC terminal mains is avail...

Page 19: ...the housing s direct mounting points for the M SHEV see Figure 15 Mounting points back of housing or mount the four wall fixing lugs see Figure 16 Wall fixing lugs supplied to the housing and then ma...

Page 20: ...10 AP Figure 18 M SHEV DANGER The system must be mounted by specialist personnel qualified electricians only All relevant national safety regulations and directives apply to mounting installation and...

Page 21: ...h RM 2860 TH 4860 1 2 3 4 5 24V Wind Rain Digital Input GND E LZ A Z E 5 NO 1 2 3 NC Jumper Power Supply 4 e g central ventilation or other external control Mains Backup wind rain detector WTS OK Y M...