Components — Central Interface (ZI-100)

BA_M-SHEV_EN_17

www.simon-protec.com

Date: 30.07.2019

[email protected]

Issue: 1.7/ 07.2019

Page 10

 — Central Interface (ZI-100)

2.4 Central Interface – ZI-100

Figure 8 

The ZI-100 is the central module of the M-SHEV modular con-
trol panel. 

The ZI-100 performs the following tasks:

• Control of the connected bus participants

• Interface for SIMON LINK

• Interface for a remote maintenance module via mobile 

communication (GPRS)

• Wind / rain detector (WTS) connection

• Digital input (e.g. for central ventilation system)

• Visual indicators:

– green LED – “OK” mode
– yellow LED – “Failure” mode
– white LED – “WTS triggered”

2.4.1 General functions

If secondary power supply is active (batteries), the yellow 
LED on the ZI-100 flashes.

2.4.2 Ventilation

2.4.2.a Wind / rain detector (WTS) connection

The wind / rain detector (WTS) automatically closes the flaps /
windows that are opened for ventilation. The signal of the 
wind / rain detector is only overridden by ALARM triggering. 
WTS must be enabled in the “Ventilation” subfolder of the 
corresponding motor relay MR-120.

2.4.3 Global ventilation button

Global ventilation buttons can be connected and 
configured at the digital inputs. At the MR-120 
modules it is possible to set whether and how to 

react to this these buttons (ZI-100 digital inputs).

2.4.4 Digital inputs

Five digital inputs can receive different functions, 
such as time switch signals. They can be evaluat-
ed independently of each other as normally open 

or normally closed. Two 24 

V DC

 terminals (mains / backup) 

are available to connect the inputs. 

The respective functions are shown in the connection plan 
according to customer requirements. Should you require any 
changes, please contact our technical sales department.

2.4.5 Maintenance counter

The M-SHEV control panels product family has a 
maintenance counter which optionally outputs a 
fault after a set time if no maintenance is carried 

out. This function is switched off by default.

2.4.6 Technical data ZI-100 (-ZI1)

Table 16 

Permissible voltage range

21 – 28.2 V DC

Power consumption

max. 30 mA

Wind / rain detector (WTS) connection

See Chapter 4.2 “Cen-
tral interface – ZI-100” 
on page 21.

Output voltage range 

(E WTS / mains operation)

1

1.

Switched off in emergency power mode

23.6 – 24.8 V DC

Current rating WTS

max. 150 mA

Digital input connection

See Chapter 4.2 “Cen-
tral interface – ZI-100” 
on page 21.

Output voltage range 

(digital input – 24 V DC mains)

2

2.

Switched off in emergency power mode

23.6 – 24.8 V DC 

Output voltage range 

(digital input – 24 V DC backup)

3

3.

Remains steady even during emergency operation

21.0 – 28.2 V DC

Current rating

max. 150 mA

SIMON LINK connection

6-pin

LED indicator

white: “WTS”

yellow: “Failure”

green: “OK”

ZI-100

 

Zentralinterface

Central Interface

M–SHEV

®

SIMON LINK

Factory-configured 

(internal

Internal

power supply)

WTS 

Connection for

BUS connection

Digital Input

connection 

 

INFORMATION

The WTS function can also be used for safe closing in 
case of mains failure. For further relevant information, see 
Chapter 2.2 “Fault mode” on page 9.

Summary of Contents for M-SHEV Series

Page 1: ...ily Copyright by SIMON PROtec Systems GmbH Subject to technical changes and errors All figures are exemplary Only valid with the supplementary sheet Safety instructions and warranty conditions Operati...

Page 2: ...0 2 4 6 Technical data ZI 100 ZI1 10 2 5 Sensor Interface SI 100 11 2 5 1 Trigger or indicating lines line monitored 11 2 5 2 Indicators 11 2 5 3 ALARM mode reset 11 2 5 4 DIP switches 11 2 5 5 Reset...

Page 3: ...time 17 2 7 3 Technical data MI 100 MI1 17 2 8 BUS Interface BI 100 optional 18 2 8 1 MODBUS 18 2 8 2 Digital inputs 18 2 8 3 Technical data BI 100 BI1 18 3 Mechanical connection 19 3 1 M SHEV 10 AP...

Page 4: ...gulation electronics for the operation of 24 V DC actuators Ventilation signals from ventilation buttons wind rain detectors and alarm triggering of three monitored indicating lines emergency button S...

Page 5: ...ties M SHEV 10 AP Dimensions W x H x D Weight including battery 14 3 kg Protection rating IP20 according to EN 60529 Housing Steel sheet powder coated Colour RAL 9010 Table 2 Mechanical properties M S...

Page 6: ...tching power supply charging device battery are used cascaded The following figures may vary depending on the size of the housing and number of modules According to EN 12101 10 both the primary switch...

Page 7: ...failure undervoltage of the power supply or if the primary power supply fails 2 1 4 Technical data rated values Table 6 Operating voltage continuous operation 230 V AC Permissible voltage range short...

Page 8: ...Fuse character type T 3 15 A Charging voltage 26 7 27 9 V DC Charging current 1 1 A Interruption time no interruption LED indicator for mains operating state Continuous green light mains present LED i...

Page 9: ...3 Internal BUS connection The individual modules of the M SHEV control panel are con nected to each other through the BUS connections RJ45 sockets 2 3 1 Terminal plugs AS 110 The AS 110 terminating pl...

Page 10: ...evaluat ed independently of each other as normally open or normally closed Two 24 V DC terminals mains backup are available to connect the inputs The respective functions are shown in the connection p...

Page 11: ...00 is provided with the following indicators Indicating line is triggered separate for B1 B2 and B3 red Failure faults of the SI 100 yellow OK operating state green 2 5 3 ALARM mode reset After a SI 1...

Page 12: ...0 SI1 Table 17 Permissible voltage range 21 28 2 V DC Power consumption standby mode 10 20 mA Power consumption ALARM mode max 80 mA Emergency button connection 7 terminals OK Y M RZ RA B1 Smoke detec...

Page 13: ...unction Basic The MR 120 module operates as standard with 3 priority levels for detection lines 1 HE button 2 smoke detector and 3 BMZ When an as signed sensor interface is triggered the MR 120 reacts...

Page 14: ...as long as the respective direction button is pressed The actuators stop as soon as the button is released If the ventilation button is touched only briefly the ventilation command is switched to cont...

Page 15: ...and closing times must be measured and then entered on site The connected actuators then move to the required position proportional to the applied supply voltage or current To ensure that this openin...

Page 16: ...ntacts A statement always consists of three elements a logical statement no entry statement is true or NOT the statement is negated the origin of the statement and the statement Origin of the statemen...

Page 17: ...ndition logical statement is true the dry contact relay is switched either as long as the condition remains true or for a preset time 1 second to 1 hour 2 7 2 c Hold time After reaching the condition...

Page 18: ...o set the parity stop bits and a watchdog function If the MODBUS communication is lost the BI 100 goes into fault mode 2 8 2 Digital inputs There are 2 digital inputs A 24 V DC terminal mains is avail...

Page 19: ...the housing s direct mounting points for the M SHEV see Figure 15 Mounting points back of housing or mount the four wall fixing lugs see Figure 16 Wall fixing lugs supplied to the housing and then ma...

Page 20: ...10 AP Figure 18 M SHEV DANGER The system must be mounted by specialist personnel qualified electricians only All relevant national safety regulations and directives apply to mounting installation and...

Page 21: ...h RM 2860 TH 4860 1 2 3 4 5 24V Wind Rain Digital Input GND E LZ A Z E 5 NO 1 2 3 NC Jumper Power Supply 4 e g central ventilation or other external control Mains Backup wind rain detector WTS OK Y M...

Page 22: ...formation for motor cable empirical formula Wire cross section mm single cable length m x number of actuators x current consumption per actuator A 73 The DIN VDE 0100 and DIN VDE 0298 regulations cont...

Page 23: ...rical fastening features i e it can be used on the right or left The lid can alternatively be equipped with a lock 5 2 M SHEV Place the pair of batteries on the bottom plate of the housing Connect the...

Page 24: ...51 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Fraunhoferstra e 14 82152 Planegg Martinsried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Mail info simon protec de Internet www simon...

Reviews: