background image

Components — Motor Relay (MR-120)

BA_M-SHEV_EN_17

www.simon-protec.com

Date: 30.07.2019

[email protected]

Issue: 1.7/ 07.2019

Page 14

2.6.2.d Retriggering function (deadlock) 

The M-SHEV product family meets the requirements of 
prEN 12101-9 with regard to deadlock, e.g. frozen NSHEVs 
(natural smoke and heat exhaust ventilation). This means that 
after an ALARM triggering, the actuators are actuated 
15   times in the OPEN direction. A new start attempt is made 
with initial short closing for 3 seconds in the CLOSE direction 
(to   protect actuators without restart interlock) at intervals of 
2   minutes. A waiting time of 500 ms is observed between 
each change of direction. After 30 minutes the triggering 
OPEN remains active.

The re-triggering function is switched off by 
default and can be individually enabled for each 
MR-120.

2.6.2.e Alarm ONLY with analog input (optional) — 

Dependency logic

With this function, the analog input is used with 
the aid of an external analog circuit as an addi-
tional condition for the execution of a ventilation 

function (dependency logic). For this purpose, the analog 
input (terminal "+") is permanently checked for a continuous 
signal (min. 0.8 mA). As long as the signal is present, an 
ALARM function can be performed. If this is not the case, 
none of the connected actuators is electrically controlled

2.6.3 Ventilation functions

The ventilation functions are only enabled in mains operation; 
if the system switches to emergency power operation, no new 
ventilation commands are accepted. Pre-existing ventilation 
commands are kept for 3 minutes

2.6.3.a Connection ventilation button /

 input ventilation signals

Two ventilation buttons or comparable ventilation signals can 
be connected in parallel to the M-SHEV. The behaviour of the 
ventilation function is influenced by the triggering type and 
duration.

It is possible to use input signals from other 
modules.

2.6.3.b Action behaviour of ventilation buttons

The dead man’s function activates automatically if the venti-
lation button is pressed for more than three seconds (auto 
dead man’s function). The dead man’s function is a safety 
function in which the actuators only move as long as the 
respective direction button is pressed. The actuators stop as 
soon as the button is released.

If the ventilation button is touched only briefly, the ventilation 
command is switched to continuous triggering. A stop func-
tion is achieved by briefly re-pressing the ventilation button in 
the OPEN direction, e.g. when opening (tip-stop function).

Each motor relay can be readjusted per ventila-
tion button connection (LT1 / LT2, mode open /
 close) ) as follows:

• auto dead man + tip-stop

• auto dead man

• no dead man + tip-stop

• no dead man

• dead man only

2.6.3.c Open delay in vent mode

The MR-120 allows you to set a start delay for 
certain applications (e.g. in combination with sun 
protection systems in front of windows). This 

ventilation triggering will be displayed immediately, received 
and processed and can be indicated by a MI-100 signal inter-
face. After the intended ventilation start delay time has been 
elapsed, the actuators move to the intended ventilation posi-
tion.

2.6.3.d WTS (wind  / rain-detector)

For each motor relay it can be defined whether it 
should react to the central WTS signal (ZI-100). 

2.6.3.e Gap ventilation

The gap ventilation function allows the user to 
open the smoke and heat exhaust / vents  up  to 
any defined stroke. The gap ventilation function 

and the gap ventilation time can be set with SIMON LINK. 
When the ventilation button is pressed, the actuators open to 
the set position or to the full opening stroke in ALARM mode. 

2.6.3.f Automatic close

This function closes the opening units automati-
cally following a freely adjustable ventilation time. 
This function is used to set the waiting time after 

which the drives are to be closed automatically. This setting 
can be parameterized in seconds (s), minutes (min) or hours 
(h) up to a maximum of 24 hours. 

ATTENTION

The continuous signal is only detected from 0.8 mA. The 
maximum      current      at      the     input     must     not     be     exceeded! 

This input is deactivated by default. 

INFORMATION

The ventilation functions can be modified on request using 
the SIMON LINK configuration software.

INFORMATION

If you change a setting at this point, please remember to 
apply a functionally identical settings to the ALARM func-
tions (see chapter 2.6.2.a “Open delay in alarm mode” on 
page 13).

ATTENTION

A new OPEN command is only accepted by the MR-120 
after the CLOSE gap ventilation time has fully elapsed.

Summary of Contents for M-SHEV Series

Page 1: ...ily Copyright by SIMON PROtec Systems GmbH Subject to technical changes and errors All figures are exemplary Only valid with the supplementary sheet Safety instructions and warranty conditions Operati...

Page 2: ...0 2 4 6 Technical data ZI 100 ZI1 10 2 5 Sensor Interface SI 100 11 2 5 1 Trigger or indicating lines line monitored 11 2 5 2 Indicators 11 2 5 3 ALARM mode reset 11 2 5 4 DIP switches 11 2 5 5 Reset...

Page 3: ...time 17 2 7 3 Technical data MI 100 MI1 17 2 8 BUS Interface BI 100 optional 18 2 8 1 MODBUS 18 2 8 2 Digital inputs 18 2 8 3 Technical data BI 100 BI1 18 3 Mechanical connection 19 3 1 M SHEV 10 AP...

Page 4: ...gulation electronics for the operation of 24 V DC actuators Ventilation signals from ventilation buttons wind rain detectors and alarm triggering of three monitored indicating lines emergency button S...

Page 5: ...ties M SHEV 10 AP Dimensions W x H x D Weight including battery 14 3 kg Protection rating IP20 according to EN 60529 Housing Steel sheet powder coated Colour RAL 9010 Table 2 Mechanical properties M S...

Page 6: ...tching power supply charging device battery are used cascaded The following figures may vary depending on the size of the housing and number of modules According to EN 12101 10 both the primary switch...

Page 7: ...failure undervoltage of the power supply or if the primary power supply fails 2 1 4 Technical data rated values Table 6 Operating voltage continuous operation 230 V AC Permissible voltage range short...

Page 8: ...Fuse character type T 3 15 A Charging voltage 26 7 27 9 V DC Charging current 1 1 A Interruption time no interruption LED indicator for mains operating state Continuous green light mains present LED i...

Page 9: ...3 Internal BUS connection The individual modules of the M SHEV control panel are con nected to each other through the BUS connections RJ45 sockets 2 3 1 Terminal plugs AS 110 The AS 110 terminating pl...

Page 10: ...evaluat ed independently of each other as normally open or normally closed Two 24 V DC terminals mains backup are available to connect the inputs The respective functions are shown in the connection p...

Page 11: ...00 is provided with the following indicators Indicating line is triggered separate for B1 B2 and B3 red Failure faults of the SI 100 yellow OK operating state green 2 5 3 ALARM mode reset After a SI 1...

Page 12: ...0 SI1 Table 17 Permissible voltage range 21 28 2 V DC Power consumption standby mode 10 20 mA Power consumption ALARM mode max 80 mA Emergency button connection 7 terminals OK Y M RZ RA B1 Smoke detec...

Page 13: ...unction Basic The MR 120 module operates as standard with 3 priority levels for detection lines 1 HE button 2 smoke detector and 3 BMZ When an as signed sensor interface is triggered the MR 120 reacts...

Page 14: ...as long as the respective direction button is pressed The actuators stop as soon as the button is released If the ventilation button is touched only briefly the ventilation command is switched to cont...

Page 15: ...and closing times must be measured and then entered on site The connected actuators then move to the required position proportional to the applied supply voltage or current To ensure that this openin...

Page 16: ...ntacts A statement always consists of three elements a logical statement no entry statement is true or NOT the statement is negated the origin of the statement and the statement Origin of the statemen...

Page 17: ...ndition logical statement is true the dry contact relay is switched either as long as the condition remains true or for a preset time 1 second to 1 hour 2 7 2 c Hold time After reaching the condition...

Page 18: ...o set the parity stop bits and a watchdog function If the MODBUS communication is lost the BI 100 goes into fault mode 2 8 2 Digital inputs There are 2 digital inputs A 24 V DC terminal mains is avail...

Page 19: ...the housing s direct mounting points for the M SHEV see Figure 15 Mounting points back of housing or mount the four wall fixing lugs see Figure 16 Wall fixing lugs supplied to the housing and then ma...

Page 20: ...10 AP Figure 18 M SHEV DANGER The system must be mounted by specialist personnel qualified electricians only All relevant national safety regulations and directives apply to mounting installation and...

Page 21: ...h RM 2860 TH 4860 1 2 3 4 5 24V Wind Rain Digital Input GND E LZ A Z E 5 NO 1 2 3 NC Jumper Power Supply 4 e g central ventilation or other external control Mains Backup wind rain detector WTS OK Y M...

Page 22: ...formation for motor cable empirical formula Wire cross section mm single cable length m x number of actuators x current consumption per actuator A 73 The DIN VDE 0100 and DIN VDE 0298 regulations cont...

Page 23: ...rical fastening features i e it can be used on the right or left The lid can alternatively be equipped with a lock 5 2 M SHEV Place the pair of batteries on the bottom plate of the housing Connect the...

Page 24: ...51 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Fraunhoferstra e 14 82152 Planegg Martinsried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Mail info simon protec de Internet www simon...

Reviews: