User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
7.18.
E-MAIL NOTIFICATIONS
This button is visible in all devices but this functionality will work only in the ones with
the E-mail notifications licence. Devices without the E-mail notification licence will
display the following message in the E-mail notifications menu:
“
Available after entering licence
”
The
E-mail notifications
menu allows to send messages using e-mail. Each message
can contain any description and attachment with selected
Logical channels
or
Groups
.
E-mail notifications can be used as devices state report when an alarm or a specified signal
occurs. This report will be sent to all the declared recipients.
In case of any sending error (e.g. connection with network error) messages can be
saved in a queue where they are waiting to be sent, however sending and saving to the queue
can not occur more often then once a minute which means that any faster than one minute
message trigger will be ignored. Additionally, this queue can not be longer than 10 messages
and when it fills up the appearance of a new message will delete the oldest one and the new
one will be placed into the queue. When the connection is re-established, the device will send
messages in the queue as one e-mail with all the awaiting attachments. All the messages
from all the queues will be lost when the device is switched off or when power fails.
There are 32 available
Messages
which can be configured independently and each of
them can be sent to several recipients.
Attachment with
Logical channels
has the following structure:
File name:
serial_number
_Ch_
data
_
hour
_
minute
_
second
_msgID=
Message_number
_
Suffix
.csv
File content – first row:
“Channel Number”,”Channel Name”,”Value”,”Unit”
File content – next rows:
selected_channel_number
,”
Channel_name
”,
Channel_value
,”
unit
”
Each Logical channel is stored in a new line of the file.
252
i
General settings
Logical channels
Built-in inputs
Built-in outputs
External outputs
Profiles/timers
Controllers
Groups
Modbus
Network settings
Access options
E-mail notifications
Device configuration