User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
Most important parameters of passive current outputs COP2 and COP4:
COP2
COP4
Number of outputs
2
4
Output type
Passive current output
Passive current output
Nominal analogue range
4 - 20 mA
4 - 20 mA
Hardware output
limitation
3 - 25 mA
3 - 25 mA
Output voltage dropout
9 V
9 V
Overload protection
Internal resettable fuse 50 mA
Internal resettable fuse 50 mA
Loop supply range
9 - 30 V
9 - 30 V
Output current precision
0.1% @ 25
C, 50 ppm/
C
0.1% @ 25
C, 50 ppm/
C
Resolution
13 bit
13 bit
Isolation strength
1 min @ 500 V AC
1 min @ 500 V AC
Tab. 8.9 Technical data for passive current outputs
Most important parameters of electronic relay outputs with PWM function:
OC2
OC4
Static parameters
Number of outputs
2
4
Max current source per
ouptut
100 mA
100 mA
Output high level voltage
(Iout = 5 mA):
(Vext. - 0.5 V)
(Vext. - 0.5 V)
Output low level voltage
(Iout = 5 mA):
< 1 V
< 1 V
Maximum external supply
of output
30 V
30 V
Dynamic parameters (set individually for every output)
PWM period*
0.1
1600 s
0.1
1600 s
PWM resolution
0.1 s
0.1 s
PWM internal frequency** 5 kHz **
5 kHz **
Pulse – duty factor
0
100%
0
100%
Pulse – duty factor
resolution
15 bits *
0x8000 means 100%
15 bits *
0x8000 means 100%
Lo state minimum time
0
800 s
0
800 s
High state minimum time 0
800 s
0
800 s
270