User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
Fig. 7.126. The connection scheme for FUN4 hardware configuration in RTD mode and
Modbus MB1 port
In the first step we define
Controller
settings:
–
touch the screen and press
Menu
button,
–
press the
Device configuration
button,
–
enter the
Controllers
menu,
–
using the arrows in the top navigation bar, select any
Controller
such as
1
,
–
in the
Controller name
parameter write
Controller 1
,
–
Mode
parameter set as
PID
,
–
in the
Dead zone
parameter write
2
,
–
for
Controller parameters
parameter block:
•
in
P coefficient
parameter write
0.3
,
•
in
I coefficient
parameter write
0.5
,
•
in
D coefficient
parameter write
0.02
,
•
Differentiated signal
parameter set as
error (deviation)
,
203
Block A
FUN4
IN1
PT
U, I
mV
TC GND
IN2
PT
U, I
mV
TC GND
IN3
PT
U, I
mV
TC GND
IN4
PT
U, I
mV
TC GND
Control system
Slave device
Slave address: 1
Register: 1h
Current
converter
Heater
PT100
sensor
0÷5A
GND
RS-485
P
E
A
B
G
N
D
RS485
D
ig
ita
l i
np
ut
G
N
D
+
24
V
Power supply
(depending on version)
RTD
Connection for
RTD mode
PT
U, I
mV
TC GND