User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
Logical channel
such as 1,
–
in the
Name
parameter write
Set point value
,
–
Mode
parameter set as
Set point value
,
–
in the
Set point
value parameter write
50
,
–
for
Displaying
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0
,
•
in
Graph low
parameter write
0
,
•
in
Graph high
parameter write
65535
,
Next two logical channels set similarly:
–
Logical channel 2
:
•
in
Name
parameter write
Valve position
,
•
in
Set point
value write
1
,
–
Logical channel 3
:
•
in
Name
parameter write
Alarm state
,
•
in
Set point
parameter write
0
,
–
all the other parameters should be on default settings,
Define external outputs. To do this:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
External outputs
menu,
–
using the arrows in the top navigation bar, select
Ext.out.:1
, (it is a linear output),
–
there are three constant parameters which are consistent
Modbus
menu
configuration:
•
Comm.port: MB2 (MASTER),
•
Device: Addr.5:”Flowmeter”,
•
Output channel: Out.1:HR 2h/+1,b.0-31,
–
for next parameters:
•
Source
parameter set as logical channel named the
Set point value
,
•
for
Input levels
block parameters:
◦
in
Lower level
parameter write
0
,
◦
in
Upper level
parameter write
65535
,
•
for
Output levels
block parameters:
◦
in
Lower level
parameter write
0
,
◦
in
Upper level
parameter write
65535
,
◦
in
Alarm level
parameter write
0
,
–
using the arrows in the top navigation bar, select
Ext.out.:2
, (it is a relay output),
–
there are three constant parameters which are consistent with the
Modbus
menu
configuration:
•
Comm.port: MB2 (MASTER),
•
Device: Addr.5:”Flowmeter”,
•
Output channel: Out.2:HR 4h, b.0,
–
for next parameters:
•
Mode
parameter set as
above level
; because we want the valve to switch on
when the value is greater than
'0'
,
171