User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-N16
In the next step you need to define a
Group
to set up logical channels to view them in
one window on the screen. To do this:
–
enter the
Group
menu to enable the e.g.
Group 2
if it is off,
–
for
Display options
block parameters:
•
in
Name
parameter write
Workplace
,
•
Bars
parameter set as
vertical
,
–
for
Channels
block parameters:
•
Slot 1
parameter set as
Logical channel 30
called the
Office
,
•
Slot 2
parameter set as
Logical channel 31
called the
Warehouse
,
•
Slot 3
parameter set as
empty
,
•
Slot 4
parameter set as
Logical channel 32
called the
Basement
,
•
Slot 5
parameter set as
Logical channel 33
called the
Corridor
,
•
Slot 6
parameter set as
empty
,
–
for
Logging options
block parameters (this block of parameters appears if you have
a license for logging):
•
Mode
parameter set as
always
, we want to register at all times until we change
the configuration to stop the registration,
•
in
Description
parameter write
Measure of Workplace temperature
, (it can be
any text),
•
Base period
parameter set as
1
,
•
Base unit
parameter set as
minute
, sampling a group of channels at 1 minute,
•
Alternative mode parameter set as disabled,
The last step is to define the Initial view displayed on the LCD screen when the device
starts. The initial view has to display a defined group of logical channels: 30, 31, 32, 33 in
the bars mode. To do this:
–
enter the
General settings
menu,
–
for
Initial view
block parameters:
•
Display
mode
parameter set as
bars
,
•
Displayed group
parameter set as
Group 2: Workplace
,
Finally, you must exit the menu by pressing the
Save changes
button. The result of the
changes will be visible after a call to the first measurement and a manual switch for displaying
Group 2. An example of the window view for 4 logical channels is shown in
Fig. 7.71. Logical channels configuration - Example 3
131