10.1
” WIRELESS HANDHELD OPERATING PANEL
HGW 1033-3
25.01.2019
Page 67
16.2.6
Emergency Stop
In the Safety Designer, in the “HGW_1033_3“ module,
Safe_Input1
and
Safe_Input2
are
used for the two-channel application of the emergency stop switch.
The emergency stop LED must be operated in compliance with the emergency stop standard
EN 13850.
WARNING
If the panel is not coupled or is off, the emergency stop switch has no func-
tion! The application must ensure that in such a case, the emergency stop
switch is not illuminated.
Si le panneau n'est pas couplé ou est éteint, l'interrupteur d'arrêt d'urgence
n'a aucune fonction! L'application doit s'assurer que, dans un tel cas, l'inter-
rupteur d'arrêt d'urgence n'est pas allumé.
After the emergency stop has been triggered, the emergency stop switch can
then only be unlocked if:
•
the cause for triggering the emergency stop has been corrected
•
the machine can be safely restarted
Après le déclenchement de l'arrêt d'urgence, l'interrupteur d'arrêt d'urgence
ne peut être déverrouillé que si :
•
la cause du déclenchement de l'arrêt d'urgence a été corrigée
•
la machine peut être redémarrée en toute sécurité
DANGER
Unlocking the emergency stop switch cannot trigger an automatic restart of
the machine.
After the application unlocks the emergency stop switch, the operator must
be prompted to run a defined activation process.
Le déverrouillage de l'interrupteur d'arrêt d'urgence ne peut pas déclencher
un redémarrage automatique de la machine.
Après que l'application ait déverrouillé l'interrupteur d'arrêt d'urgence, l'opé-
rateur doit être invité à exécuter un processus d'activation défini.