ReversaMatic
This routine involves swapping the Up and Down transducers on the pipe (while keeping the
cables attached) such that the difference in the transit-time change represents the zero offset.
The fixed zero offset value is stored in memory in the same manner as described in Actual
Zero. This routine would generally be used whenever flow cannot be stopped and the
transducers cannot be mounted in the Reflect Mode configuration. Flow must be stable during
the entire process.
ZeroMatic
When ZeroMatic is invoked the flowmeter first performs the same analysis as described above
in the AutoZero routine. However, after this analysis is complete the flowmeter continues to
interrogate the pipe wall signal and update the zero offset value under normal operation, such
that the flowmeter dynamically compensates for changing conditions which would normally
result in zero drift. ZeroMatic will only operate with the sensors mounted in the Reflect Mode
configuration and is recommended for applications which experience large temperature
extremes.
Note
Invoking ZeroMatic will clear any existing "fixed" or memorized zero offset. If any zero offset
remains after flow is stopped, an Actual Zero can be performed without interrupting ZeroMatic
operation. To disable ZeroMatic, invoke it again, but then press <Left Arrow> to abort the
installation.
Note
The ZeroClr command only resets the memorized zero offset registers not those set when
the AutoZero routine is invoked.
Using Actual Zero
Note
Flow must be stopped with the line blocked (if possible) before invoking this function.
To invoke Actual Zero:
1. Access the [Zero Flow Adjust] option list by pressing <Right Arrow>.
2. Press <ENT>. A pop-up window prompts you to set the current flow rate (in selected rate
units) to equal zero (0.000).
Note
If a flow offset is desired (i.e., to test analog outputs) then press <Right Arrow> to enable
numeric entry.
3. Press <ENT> to start the Actual Zero process.
Connecting
5.3 Zero Flow Adjust Menu
FUP1010 IP67 Portable Flowmeter
Operating Instructions, 02/2010, A5E02951522A Revision 01
61
Summary of Contents for SITRANS FUP1010
Page 2: ......
Page 66: ......
Page 136: ......
Page 138: ......
Page 150: ......
Page 153: ...1010WP 7 21614 C ...
Page 154: ...1010WP 7 21614 C ...
Page 155: ...1010WDP 7 21614 C ...
Page 156: ...1010WDP 7 21614 C ...
Page 157: ...1010WP 8 21614 C ...
Page 158: ...1010WDP 8 21614 C ...
Page 159: ......
Page 161: ...1012FP 8 DIRECT MODE REFLECT MODE INSTALLED ON PIPE 21614 C ...
Page 162: ...1011PPS 8 TRANSDUCER PART NUMBER L H W NET WT PAIR X Z 21614 C SIZES A B C D SIZE E ...
Page 163: ...21614 C ...
Page 164: ......
Page 165: ......
Page 166: ......
Page 167: ......
Page 168: ...21614 C ...
Page 169: ...21614 C ...
Page 170: ...21614 C ...
Page 171: ...21614 C ...
Page 172: ...21614 C ...
Page 173: ...21614 C ...
Page 174: ...21614 C ...
Page 175: ...1015BC 1W 8 21614 C ...
Page 176: ......
Page 177: ...21614 C ...
Page 178: ...21614 C ...
Page 179: ...1012TP S 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TP S SERIES 21614 C MOUNTING TRACK ...
Page 180: ...REFLECT MODE DIRECT MODE 21614 C ...
Page 181: ...21614 C ...
Page 182: ...1015BC 1 8 21614 C ...
Page 183: ...21614 C INPUT OUTPUT TERMINALS 1015WP T10 8 ...
Page 184: ...21614 C INPUT OUTPUT TERMINALS 1015WP T26 8 ...
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 190: ...DUAL HEAD CONFIGURATION 21614 C IN LINE CONFIGURATION FLOW ...
Page 191: ......
Page 192: ......
Page 194: ......
Page 204: ......
Page 206: ......
Page 207: ......