Functions
5.6 Functions of the outputs
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
41
5.5.3
Thermistor input / connection on 3RW40 2 to 3RW40 4
24 V AC/DC rated control voltage
After removing the copper jumper between T11/21 and T22, you can connect and evaluate
either a Klixon thermistor integrated in the motor winding (at terminal T11/T21-T22) or a type
A PTC (at terminal T11/T21-T12).
5.6
Functions of the outputs
5.6.1
3RW30: Output terminal 13 / 14 ON
The potential-free output contact at terminal 13/14 (ON) closes if a signal is present at
terminal 1 (IN); it remains closed until the start command is removed.
The output can be used, for instance, to control a line contactor connected upstream or to
implement latching if you selected pushbutton control. For recommended circuits, refer to
chapter Typical circuit diagrams [Page 167].
Klixon
Type A PTC
ϑ
T11/T21 T12 T22
ϑ
ϑ
T22
T12
ϑ
T11/T21
t
U
S
U
N
U
R on
t
R on
t
ON 13/14
t
R on
t
IN 1
t