Installation
7.1 Installing the soft starter
SIRIUS 3RW30 / 3RW40
54
Manual, 01/2010, 535 1995-02 DS01
7.1.3
Mounting dimensions, clearances, and assembly type
The minimum clearances from other devices must be complied with to ensure unobstructed
cooling as well as the free supply and discharge of air to and from the heat sink.
Figure
NOTICE
7-1
Clearances from other devices
MLFB
a (mm)
a (in)
b (mm)
b (in)
c (mm)
c (in)
3RW30 1./3RW30 2.
15
0.59
60
2.36
40
1.56
3RW30 3./3RW30 4
30
1.18
60
2.36
40
1.56
3RW40 2.
15
0.59
60
2.36
40
1.56
3RW40 3./3RW40 4.
30
1.18
60
2.36
40
1.56
3RW40 5./3RW40 7.
5
0.2
100
4
75
3
1
1
3
5
2
4
6
a
a
E
F
Allow sufficient clearances for the cooling air to circulate freely. The device is ventilated from
bottom to top.