Functions
5.3 Motor protection / intrinsic device protection (3RW40 only)
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
33
The two types of protection must be combined to achieve full motor protection. This
combination is recommended to protect the motor optimally.
Motor overload protection
The current flow during motor operation is measured by measuring the current with
transformers integrated in the soft starter. The temperature rise in the winding is calculated
based on the rated operational current set for the motor.
A trip is generated by the soft starter when the characteristic is reached, depending on the trip
class (CLASS setting).
ATEX
"Increased safety" type of protection EEx e acc. to ATEX Directive 94/9/EC
The SIRIUS 3RW40 soft starter sizes S0 to S12 are suitable for starting explosion-proof
motors with the "increased safety" type of protection EEx e (type of protection / marking: Ex II
(2) GD).
Wire the fault output (95 96) to an upstream switching device in such a way that if a fault
occurs, this device disconnects the feeder (refer to Fig. "3RW40 wiring fault with 3RV").
Figure 5-5
3RW40 wiring fault
Note
Thermistor motor protection evaluation
The thermistor motor protection evaluation function is optionally available for the SIRIUS
3RW40 2 to 3RW40 4 soft starters in the 24 V AC/DC control voltage version.
0
a
)
4
57
5:
4
$
$
5:
$ $ ,1
21
1/
//
Summary of Contents for SIRIUS 3RW40
Page 1: ...Soft starters SIRIUS 3RW30 3RW40 Manual 01 2010 Industrial Controls Answers for industry ...
Page 2: ......
Page 68: ...Connecting 9 1 Electrical connection SIRIUS 3RW30 3RW40 68 Manual 01 2010 535 1995 02 DS01 ...
Page 210: ...Index SIRIUS 3RW30 3RW40 210 Manual 01 2010 535 1995 02 DS01 ...
Page 211: ......