ON time and switching frequency
Based on the rated motor current and the startup class, the SIRIUS 3RW30 and 3RW40 soft
starters are dimensioned for a maximum permissible switching frequency in combination with
a relative ON time (refer to chapter Technical data [Page 121]). If these values are exceeded,
a larger soft starter may have to be selected.
ON time
The relative ON time in % is the ratio between the load duration and the cycle duration for
loads that are frequently switched on and off.
The ON time (OT) can be calculated using the following formula:
where:
OT = ON time [%]
t
s
= ramp-up time [s]
t
b
= operating time [s]
t
p
= idle time [s]
The following diagram illustrates this process.
Figure 11-1
ON time
Switching frequency
The maximum permissible switching frequency must not be exceeded because the devices
could be damaged due to thermal overloading.
Optional additional fan
The switching frequency of the 3RW40 2. to 3RW40 4. soft starters can be increased by
installing an optional additional fan. For information about factors and how to determine the
maximum switching frequency if an additional fan is installed, refer to chapter Calculating the
permissible switching frequency [Page 81].
27
W
V
W
E
W
V
W
E
W
S
W
W
V
W
E
W
S
,
H
Summary of Contents for SIRIUS 3RW40
Page 1: ...Soft starters SIRIUS 3RW30 3RW40 Manual 01 2010 Industrial Controls Answers for industry ...
Page 2: ......
Page 68: ...Connecting 9 1 Electrical connection SIRIUS 3RW30 3RW40 68 Manual 01 2010 535 1995 02 DS01 ...
Page 210: ...Index SIRIUS 3RW30 3RW40 210 Manual 01 2010 535 1995 02 DS01 ...
Page 211: ......