Typical circuit diagrams
15.10 3RW and contactor for emergency starting
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
191
15.10
3RW and contactor for emergency starting
15.10.1
3RW30 and contactor for emergency starting
Figure
WARNING
15-29 Wiring of the 3RW30 control and main circuits
(1) For the permissible values for the main and control voltage (dependent on the MLFB),
refer to chapter Technical data [Page 121] .
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type
of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter
Technical data [Page 121]
'LUHFWVWDUWLQJ
6WDUWVWRS
'LUHFWVWDUWHU
FRQWDFWRU
6W
DU
W
21
6HOHFWRUVZLWFK
6RIWVWDUW
/
1
4
8
4
$
$
+
7
/
7
/
7
/
4
4
5:
4
0
:
9
8
0
,!!
,!!
,!!
$
$
4
6
)
)
(2) Automatic restart. Can result in death, serious injury, or property damage.
Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to
Troubleshooting chapter) are automatically reset when the system returns to normal. An
automatic restart is initiated and the 3RW restarted if a start command is present at the input.
If you do not want the motor to start automatically, you must integrate suitable additional
components, e.g. phase failure or load monitoring devices, into the control and main circuits.
Summary of Contents for SIRIUS 3RW40
Page 1: ...Soft starters SIRIUS 3RW30 3RW40 Manual 01 2010 Industrial Controls Answers for industry ...
Page 2: ......
Page 68: ...Connecting 9 1 Electrical connection SIRIUS 3RW30 3RW40 68 Manual 01 2010 535 1995 02 DS01 ...
Page 210: ...Index SIRIUS 3RW30 3RW40 210 Manual 01 2010 535 1995 02 DS01 ...
Page 211: ......