Functions
5.7 Diagnostics and fault signals
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
45
Fault
Cause
Remedy
Impermissible electronics supply
voltage
The control supply voltage does not
correspond to the soft starter's rated
voltage.
Check the control supply voltage; an
incorrect control supply voltage could be
caused by a power failure or a voltage
dip.
Bypass overload
A current > 3.5 x I
e
of the soft starter
occurs for > 60 ms in bypass mode (e.g.
because the motor is blocked).
Check the motor and load, and check the
soft starter's dimensions.
Missing load voltage, phase failure
/ missing load
Cause 1: Phase L1 / L2 / L3 is missing or
fails / collapses when the motor is
operating.
Tripped as a result of a dip in the
permissible rated operational voltage >
15 % for > 100 ms during the startup
process or > 200 ms in bypass mode.
Connect L1 / L2 / L3 or correct the voltage
dip.
Cause 2: The motor that is connected is
too small and the fault occurs as soon as
it is switched to bypass mode.
If less than 10 % of the soft starter's rated
current is flowing, the motor cannot be
operated with soft starter. Use another
soft starter.
Cause 3: Motor phase T1 / T2 / T3 is not
connected.
Connect the motor properly (e.g. jumpers
in the motor terminal box, repair switch
closed etc.)
Device fault
Soft starter defective.
Contact your SIEMENS partner or
Technical Assistance.