Installation / mounting
8.4 Soft starter with line contactor (type of coordination 1)
SIRIUS 3RW30 / 3RW40
60
Manual, 01/2010, 535 1995-02 DS01
8.4
Soft starter with line contactor (type of coordination 1)
If electrical isolation is specified, you can install a motor contactor between the soft starter and
the motor starter protector.
Figure
NOTICE
8-2
Block diagram of a feeder with an optional main / line contactor
L2
L1
L3
PE
3/N/PE~ 50 Hz 400 V
4
4
4
0
8
:
8
9
:
9
8
:
8
9
:
9
Note
For the component design, refer to chapter Technical data [Page 121].
If a main or line contactor is used, it should not be connected between the soft starter and the
motor. The soft starter could otherwise indicate a "Missing load voltage" fault in case of a
start command and delayed connection of the contactor.