2 Functions
217
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2.12.7 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
3101
Sens. Gnd Fault
OFF
ON
Alarm Only
OFF
(Sensitive) Ground Fault
3102
CT Err. I1
0.001 .. 1.600 A
0.050 A
Current I1 for CT Angle
Error
3102
CT Err. I1
1A
0.05 .. 35.00 A
1.00 A
Current I1 for CT Angle
Error
5A
0.25 .. 175.00 A
5.00 A
3103
CT Err. F1
0.0 .. 5.0
°
0.0
°
CT Angle Error at I1
3104
CT Err. I2
0.001 .. 1.600 A
1.000 A
Current I2 for CT Angle
Error
3104
CT Err. I2
1A
0.05 .. 35.00 A
10.00 A
Current I2 for CT Angle
Error
5A
0.25 .. 175.00 A
50.00 A
3105
CT Err. F2
0.0 .. 5.0
°
0.0
°
CT Angle Error at I2
3106
VPH MIN
10 .. 100 V
40 V
L-Gnd Voltage of Faulted
Phase Vph Min
3107
VPH MAX
10 .. 100 V
75 V
L-Gnd Voltage of Unfault-
ed Phase Vph Max
3108
64-1 VGND
1.8 .. 200.0 V
40.0 V
64-1 Ground Displace-
ment Voltage
3109
64-1 VGND
1.8 .. 170.0 V
40.0 V
64-1 Ground Displace-
ment Voltage
3110
64-1 VGND
10.0 .. 225.0 V
70.0 V
64-1 Ground Displace-
ment Voltage
3111
T-DELAY Pickup
0.04 .. 320.00 sec;
∞
1.00 sec
Time-DELAY Pickup
3112
64-1 DELAY
0.10 .. 40000.00 sec;
∞
10.00 sec
64-1 Time Delay
3113
50Ns-2 PICKUP
0.001 .. 1.500 A
0.300 A
50Ns-2 Pickup
3113
50Ns-2 PICKUP
1A
0.05 .. 35.00 A
10.00 A
50Ns-2 Pickup
5A
0.25 .. 175.00 A
50.00 A
3114
50Ns-2 DELAY
0.00 .. 320.00 sec;
∞
1.00 sec
50Ns-2 Time Delay
3115
67Ns-2 DIRECT
Forward
Reverse
Non-Directional
Forward
67Ns-2 Direction
3117
50Ns-1 PICKUP
0.001 .. 1.500 A
0.100 A
50Ns-1 Pickup
3117
50Ns-1 PICKUP
1A
0.05 .. 35.00 A
2.00 A
50Ns-1 Pickup
5A
0.25 .. 175.00 A
10.00 A
3118
50Ns-1 DELAY
0.00 .. 320.00 sec;
∞
2.00 sec
50Ns-1 Time delay
3119
51Ns PICKUP
0.001 .. 1.400 A
0.100 A
51Ns Pickup
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...