2 Functions
121
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
are set at addresses
2005
67c-TOC PICKUP
,
2006
67c-TOC T-DIAL
, and
2007
67c-TOC T-DIAL
respectively.
Directional 67/67N
Elements (ground)
The dynamic pickup values and time delays associated with directional overcurrent
ground protection are set at address block 21 (
gU/AMZ E dynP.
):
The dynamic pickup and delay settings for the 67N-2 element are set at addresses
2101
67Nc-2 PICKUP
and
2102
67Nc-2 DELAY
respectively; the dynamic pickup
and delay settings for the 67N-1 element are set at addresses
2103
67Nc-1 PICKUP
and
2104
67Nc-1 DELAY
respectively; and the pickup, time multiplier (for IEC curves
or user-defined curves), and time dial (for ANSI curves) settings for the 67N-TOC
element are set at addresses
2105
67Nc-TOC PICKUP
,
2106
67Nc-TOC T-DIAL
,
2107
67Nc-TOC T-DIAL
, respectively.
2.4.3
Settings
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
1701
COLDLOAD PICKUP
OFF
ON
OFF
Cold-Load-Pickup Func-
tion
1702
Start Condition
No Current
Breaker Contact
79 ready
No Current
Start Condition
1703
CB Open Time
0 .. 21600 sec
3600 sec
Circuit Breaker OPEN
Time
1704
Active Time
1 .. 21600 sec
3600 sec
Active Time
1705
Stop Time
1 .. 600 sec;
∞
600 sec
Stop Time
1801
50c-2 PICKUP
1A
0.10 .. 35.00 A;
∞
10.00 A
50c-2 Pickup
5A
0.50 .. 175.00 A;
∞
50.00 A
1802
50c-2 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50c-2 Time Delay
1803
50c-1 PICKUP
1A
0.10 .. 35.00 A;
∞
2.00 A
50c-1 Pickup
5A
0.50 .. 175.00 A;
∞
10.00 A
1804
50c-1 DELAY
0.00 .. 60.00 sec;
∞
0.30 sec
50c-1 Time Delay
1805
51c PICKUP
1A
0.10 .. 4.00 A
1.50 A
51c Pickup
5A
0.50 .. 20.00 A
7.50 A
1806
51c TIME DIAL
0.05 .. 3.20 sec;
∞
0.50 sec
51c Time dial
1807
51c TIME DIAL
0.50 .. 15.00 ;
∞
5.00
51c Time dial
1901
50Nc-2 PICKUP
1A
0.05 .. 35.00 A;
∞
7.00 A
50Nc-2 Pickup
5A
0.25 .. 175.00 A;
∞
35.00 A
1902
50Nc-2 DELAY
0.00 .. 60.00 sec;
∞
0.00 sec
50Nc-2 Time Delay
1903
50Nc-1 PICKUP
1A
0.05 .. 35.00 A;
∞
1.50 A
50Nc-1 Pickup
5A
0.25 .. 175.00 A;
∞
7.50 A
1904
50Nc-1 DELAY
0.00 .. 60.00 sec;
∞
0.30 sec
50Nc-1 Time Delay
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...