2.25 Breaker Control
362
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2.25.5 Command Logging
During the processing of the commands, independent of the further message routing
and processing, command and process feedback information are sent to the message
processing centre. These messages contain information on the cause. With the cor-
responding allocation (configuration) these messages are entered in the event list,
thus serving as a report.
Prerequisites
A listing of possible operating messages and their meaning as well as the command
types needed for tripping and closing of the switchgear or for raising and lowering of
transformer taps are described in the SIPROTEC 4 System Description.
2.25.5.1 Description
Acknowledgement
of Commands to
the Device Front
All messages with the source of command LOCAL are transformed into a correspond-
ing response and shown in the display of the device.
Acknowledgement
of commands to
Local / Remote /
DIGSI
The acknowledgement of messages with source of command Local/ Remote/DIGSI
are sent back to the initiating point independent of the routing (configuration on the
serial digital interface).
The acknowledgement of commands is therefore not executed by a response indica-
tion as it is done with the local command but by ordinary command and feedback in-
formation recording.
Monitoring of Feed-
back Information
The processing of commands monitors the command execution and timing of feed-
back information for all commands. At the same time the command is sent, the moni-
toring time is started (monitoring of the command execution). This time controls
whether the device achieves the required final result within the monitoring time. The
monitoring time is stopped as soon as the feedback information arrives. If no feedback
information arrives, a response "Timeout command monitoring time" appears and the
process is terminated.
Commands and information feedback are also recorded in the event list. Normally the
execution of a command is terminated as soon as the feedback information (
FB+
) of
the relevant switchgear arrives or, in case of commands without process feedback in-
formation, the command output resets and a message is output.
The "plus" sign appearing in a feedback information confirms that the command was
successful. The command was as expected, in other words positive. The "minus" is a
negative confirmation and means that the command was not executed as expected.
Command Output
and Switching
Relays
The command types needed for tripping and closing of the switchgear or for raising
and lowering of transformer taps are described in the configuration section of the
SIPROTEC 4 System Description /1/.
■
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...