2 Functions
247
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Note Regarding
Settings List for Au-
tomatic Reclosure
Function
The setting options of address
7137
Cmd.via control
are generated dynamically
according to the current configuration.
Address
7138
Internal SYNC
is only available for 7SJ64.
2.14.7 Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
7101
FCT 79
OFF
ON
OFF
79 Auto-Reclose Function
7103
BLOCK MC Dur.
0.50 .. 320.00 sec; 0
1.00 sec
AR blocking duration after manual
close
7105
TIME RESTRAINT
0.50 .. 320.00 sec
3.00 sec
79 Auto Reclosing reset time
7108
SAFETY 79 ready
0.01 .. 320.00 sec
0.50 sec
Safety Time until 79 is ready
7113
CHECK CB?
No check
Chk each cycle
No check
Check circuit breaker before AR?
7114
T-Start MONITOR
0.01 .. 320.00 sec;
∞
0.50 sec
AR start-signal monitoring time
7115
CB TIME OUT
0.10 .. 320.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
7116
Max. DEAD EXT.
0.50 .. 1800.00 sec;
∞
100.00 sec
Maximum dead time extension
7117
T-ACTION
0.01 .. 320.00 sec;
∞
∞
sec
Action time
7118
T DEAD DELAY
0.0 .. 1800.0 sec;
∞
1.0 sec
Maximum Time Delay of Dead-
Time Start
7127
DEADTIME 1: PH
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Phase Fault
7128
DEADTIME 1: G
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Ground Fault
7129
DEADTIME 2: PH
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Phase Fault
7130
DEADTIME 2: G
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Ground Fault
7131
DEADTIME 3: PH
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Phase Fault
7132
DEADTIME 3: G
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Ground Fault
7133
DEADTIME 4: PH
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Phase Fault
7134
DEADTIME 4: G
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Ground Fault
7135
# OF RECL. GND
0 .. 9
1
Number of Reclosing Cycles
Ground
7136
# OF RECL. PH
0 .. 9
1
Number of Reclosing Cycles
Phase
7137
Cmd.via control
(Setting options depend
on configuration)
None
Close command via control
device
7138
Internal SYNC
(Setting options depend
on configuration)
None
Internal 25 synchronisation
7139
External SYNC
YES
NO
NO
External 25 synchronisation
7140
ZONE SEQ.COORD.
OFF
ON
OFF
ZSC - Zone sequence coordina-
tion
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...