4 Technical Data
481
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
4.10
Negative Sequence Protection 46-TOC
Setting Ranges / Increments
Functional Limit
Trip Time Curves acc. to IEC
Pickup value 46-TOC
for
I
Nom
=
1 A
0.10 A to 2.00 A
Increments 0.01 A
for
I
Nom
=
5 A
0.50 A to 10.00 A
Time Multiplier T
I2p
(IEC)
0.05 s to 3.20 s or
∞
(disabled) Increments 0.01 s
Time Multiplier D
I2p
(ANSI)
0.50 s to 15.00 s or
∞
(disabled) Increments 0.01 s
Functional Limit
for
I
Nom
=
1 A
All phase currents
≤
4 A
for
I
Nom
=
5 A
All phase currents
≤
20 A
See also Figure 4-7
The trip times for
I
2
/
I
2p
≥
20 are identical to those for
I
2
/
I
2p
= 20.
Pickup Threshold
Approx. 1.10·
I
2p
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...