2.2 Overcurrent Protection 50, 51, 50N, 51N
64
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The following figures show the logic diagrams for the current elements 50-1 and 50N-
1.
Figure 2-5
Logic diagram of the 50-1 current element for phases
The dropout delay only operates if no inrush was detected. An incoming inrush will
reset a running dropout delay time.
If parameter
MANUAL CLOSE
is set to
50 -1 instant.
and manual close detection
applies, the trip is initiated as soon as the pickup conditions arrive, even if the element
is blocked via binary input. The same applies to 79AR 50-1 instantaneous.