2 Functions
211
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Logarithmic
Inverse
characteristic with
Knee Point (inverse
time)
The logarithmic inverse characteristic with knee point (see figure 2-76) is set by means
of the parameters
3119
51Ns PICKUP
,
3127
51Ns I T min
,
3128
51Ns I T
knee
,
3132
51Ns TD
,
3140
51Ns T min
and
3141
51Ns T max
.
51Ns T min
and
51Ns T max
define the range of the tripping time where
51Ns T max
is assigned
to the current threshold
51Ns PICKUP
and
51Ns T min
to the current threshold
51Ns I T min
. The knee-point time
51Ns T knee
specifies the tripping time in the
transition point of two characteristic segments with different slope. The transition point
is defined by the current threshold
51Ns I T knee
.
51Ns PICKUP
is the minimum
pickup threshold for the ground-fault pickup current of the overcurrent element. The
tripping time will assume a constant value after reaching a maximum secondary
current of 1.4 A at the latest. The parameter
51Ns TD
serves as time multiplier for the
tripping time.
Figure 2-76
Trip-time characteristics of the inverse-time ground fault protection 51Ns with
logarithmic inverse characteristic with knee point (example for 51Ns = 0.004 A)
User Defined
characteristics (In-
verse Time)
If a user-defined characteristic is configured at address
131
,
Sens. Gnd Fault
User Defined PU
, it should be noted that there is a safety factor of 1.1 between
pickup and setting value - as is standard for inverse curves. This means that pickup
will only be initiated when current of 1.1 times the setting value flows.
Entry of the value pair (current and time) is a multiple of the settings at addresses
3119
51Ns PICKUP
and
3120
51NsTIME DIAL
. Therefore, it is recommended that
these addresses are initially set to 1.00 for simplicity. Once the curve is entered, the
settings at addresses
3119
and/or
3120
may be modified if necessary.
The default setting of current values is
∞
. They are, therefore, not enabled — and no
pickup or tripping of these protective functions will occur.
Up to 20 pairs of values (current and time) may be entered at address
3131
M.of
PU TD
. The device then approximates the characteristic, using linear interpolation.
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...