2.1 General
48
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2.1.3.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
201
CT Starpoint
towards Line
towards Busbar
towards Line
CT Starpoint
202
Vnom PRIMARY
0.10 .. 800.00 kV
12.00 kV
Rated Primary Voltage
203
Vnom SECONDARY
100 .. 225 V
100 V
Rated Secondary Voltage
(L-L)
204
CT PRIMARY
10 .. 50000 A
100 A
CT Rated Primary Current
205
CT SECONDARY
1A
5A
1A
CT Rated Secondary
Current
206A
Vph / Vdelta
1.00 .. 3.00
1.73
Matching ratio Phase-VT
To Open-Delta-VT
209
PHASE SEQ.
A B C
A C B
A B C
Phase Sequence
210A
TMin TRIP CMD
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command
Duration
211A
TMax CLOSE CMD
0.01 .. 32.00 sec
1.00 sec
Maximum Close
Command Duration
212
BkrClosed I MIN
1A
0.04 .. 1.00 A
0.04 A
Closed Breaker Min.
Current Threshold
5A
0.20 .. 5.00 A
0.20 A
213
VT Connect. 3ph
Van, Vbn, Vcn
Vab, Vbc, VGnd
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
Van, Vbn, Vcn
VT Connection, three-
phase
214
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
215
Distance Unit
km
Miles
km
Distance measurement
unit
217
Ignd-CT PRIM
1 .. 50000 A
60 A
Ignd-CT rated primary
current
218
Ignd-CT SEC
1A
5A
1A
Ignd-CT rated secondary
current
235A
ATEX100
NO
YES
NO
Storage of th. Replicas w/o
Power Supply
240
VT Connect. 1ph
NO
Van
Vbn
Vcn
Vab
Vbc
Vca
NO
VT Connection, single-
phase
250A
50/51 2-ph prot
ON
OFF
OFF
50, 51 Time Overcurrent
with 2ph. prot.
Summary of Contents for siprotec SJ62
Page 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Page 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...