Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
50
Operating Instructions, 07/2012, A5E03728167
Parameter
Description
Factory
default
Default for
Cn008
Remarks
P0731[0]
BI: Function of digital output 1
52.3
52.2
Inverter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Inverter fault active
Connection macro Cn009 - PID control with the fixed value reference
OK
OK
M
M
10V AI 1 AI 2 0V DI 1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1+ DO1-
P+ N-
DO2
0V
0V
0~20mA=
0~50/60Hz
220V
N
212))
PID controller
$FWXDOYDOXH
)L[HG3,'VHWSRLQW
)L[HG3,'VHWSRLQW
)L[HG3,'VHWSRLQW
)DXOW
5XQQLQJ
6SHHG
aP$
Connection macro settings:
Parameter
Description
Factory
default
Default for
Cn009
Remarks
P0700[0]
Selection of command source
1
2
Terminals as command source
P0701[0]
Function of digital input 1
0
1
ON / OFF
P0702[0]
Function of digital input 2
0
15
DI2 = PID fixed value 1
P0703[0]
Function of digital input 3
9
16
DI3 = PID fixed value 2
P0704[0]
Function of digital input 4
15
17
DI4 = PID fixed value 3
P2200[0]
Enable PID controller
0
1
Enable PID
P2216[0]
Fixed PID setpoint mode
1
1
Direct selection
P2220[0]
BI: Fixed PID setpoint select bit 0
722.3
722.1
BICO connection DI2
P2221[0]
BI: Fixed PID setpoint select bit 1
722.4
722.2
BICO connection DI3
P2222[0]
BI: Fixed PID setpoint select bit 2
722.5
722.3
BICO connection DI4
P2253[0]
CI: PID setpoint
0
2224
PID setpoint = fixed value
P2264[0]
CI: PID feedback
755.0
755.1
PID feedback = AI2