Parameter list
7.1 Introduction to parameters
SINAMICS V20 Inverter
120
Operating Instructions, 07/2012, A5E03728167
Data type
The data types available are shown in the table below.
U8
8-bit unsigned
U16
16-bit unsigned
U32
32-bit unsigned
I16
16-bit integer
I32
32-bit integer
Float
32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source) the following combinations are possible when creating BICO
interconnections:
BICO input parameter
CI parameter
BI parameter
BICO output parameter
U32 / I16
U32 / I32
U32 / Float
U32 / Bin
CO: U8
√
√
-
-
CO: U16
√
√
-
-
CO: U32
√
√
-
-
CO: I16
√
√
-
-
CO: I32
√
√
-
-
CO: Float
√
√
√
-
BO: U8
-
-
-
√
BO: U16
-
-
-
√
BO: U32
-
-
-
√
BO: I16
-
-
-
√
BO: I32
-
-
-
√
BO: Float
-
-
-
-
Legend:
√: BICO interconnection permitted
-: BICO interconnection not permitted
Scaling
Specification of the reference quantity with which the signal value will be converted
automatically.
Reference quantities, corresponding to 100 %, are required for the statement of physical
units as percentages. These reference quantities are entered in P2000 ... P2004.
In addition to P2000 ... P2004 the following normalizations are used:
●
TEMP: 100 °C = 100 %
●
PERCENT: 1.0 = 100 %
●
4000H: 4000 hex = 100 %