For example, copying of all values from CDS0 to CDS2 can be accomplished by the
following procedure:
1.
Set P0809[0] = 0: copy from CDS0
2.
Set P0809[1] = 2: copy to CDS2
3.
Set P0809[2] = 1: start copy
Command data set
The command data sets are changed over using the BICO parameters P0810 and P0811,
whereby the active command data set is displayed in parameter r0050. Changeover is
possible in both the "Ready" and the "Run" states.
P0810 = 0
P0811 = 0
CDS0
P0810 = 1
P0811 = 0
CDS1
P0810 = 0 or 1
P0811 = 1
CDS2
Inverter data set
The inverter data sets are changed over using the BICO parameters P0820 and P0821,
whereby the active inverter data set is displayed in parameter r0051. Inverter data sets can
only be changed over in the "Ready" state.
P0820 = 0
P0821 = 0
DDS0
P0820 = 1
P0821 = 0
DDS1
P0820 = 0 or 1
P0821 = 1
DDS2
BI, BO, CI, CO, CO / BO in parameter names
NOTICE
To view BICO parameters, see "Index" at the end of this manual.
Certain parameter names include the following abbreviated prefixes: BI, BO, CI, CO and CO
/ BO followed by a colon. These abbreviations have the following meanings:
BI
=
(0)
P9999
Binector input: Parameter selects the source of a binary signal
BO
=
r9999
r9999
r9999
Binector output: Parameter connects as a binary signal
CI
=
(999:9)
r9999
Connector input: Parameter selects the source of an analog signal
CO
=
r9999 [99]
Connector output: Parameter connects as an analog signal
CO / BO =
r9999
r9999
Connector / binector output: Parameter connects as an analog signal and / or as
a binary signal