Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
102
Operating Instructions, 07/2012, A5E03728167
5.6.3.15
Setting the user default parameter set
Functionality
The user default parameter set allows a modified set of defaults, different to the factory
defaults, to be stored. Following a parameter reset these modified default values would be
used. An additional factory reset mode would be required to erase the user defaults and
restore the inverter to factory default parameter set.
Creating the user default parameter set
1.
Parameterize the inverter as required.
2.
Set P0971 = 21, and the current inverter state is now stored as the user default.
Modifying the user default parameter set
1.
Return the inverter to the default state by setting P0010 = 30 and P0970 = 1. The inverter
is now in the user default state if configured, else factory default state.
2.
Parameterize the inverter as required.
3.
Set P0971 = 21 to store current state as the user default.
Setting parameters
Parameter
Function
Setting
P0010
Commissioning parameter
This parameter filters parameters so that only those related to
a particular functional group are selected. It must be set to 30
in order to store or delete user defaults.
= 30: Factory setting
P0970
Factory reset
This parameter resets all parameters to their user default /
factory default values.
= 1: Parameter reset to user defaults if stored else factory
defaults
= 21: Parameter reset to factory defaults deleting user
defaults if stored
P0971
Transfer data from RAM to EEPROM This parameter transfers values from RAM to EEPROM.
= 1: Start transfer
= 21: Start transfer and store parameter changes as user
default values
For information about restoring the inverter to factory defaults, refer to Section "Restoring to